Whirlpool WEG515S0FS Installation Guide - Page 7

Gas Pressure Regulator, Burner Input Requirements, Gas Supply Pressure Testing - canada

Page 7 highlights

Flexible Metal Appliance Connector: ■■ If local codes permit, a new CSA design-certified, 4 to 5 ft (122 to 152.4 cm) long, ½" or ¾" (1.3 or 1.9 cm) I.D. (inside diameter), flexible metal appliance connector may be used for connecting range to the gas supply line. ■■ A ½" (1.3 cm) male pipe thread is needed for connection to the female pipe threads of the inlet to the appliance pressure regulator. ■■ Do not kink or damage the flexible metal tubing when moving the range. ■■ Must include a shut-off valve: The supply line must be equipped with a manual shut-off valve. This valve should be located in the same room but external to the range opening, such as an adjacent cabinet. It should be in a location that allows ease of opening and closing. Do not block access to shut-off valve. The valve is for turning on or shutting off gas to the range. B A C A. Gas supply line B. Shut-off valve "open" position C. To range Gas Pressure Regulator The gas pressure regulator supplied with this range must be used. The inlet pressure to the regulator should be as follows for proper operation: Natural Gas: Minimum pressure: 6" WCP Maximum pressure: 14" WCP LP Gas: Minimum pressure: 12" WCP Maximum pressure: 14" WCP Contact local gas supplier if you are not sure about the inlet pressure. Burner Input Requirements Input ratings shown on the model/serial/rating plate are for elevations up to 2,000 ft (609.6 m). For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4% for each 1,000 ft (304.8 m) above sea level (not applicable for Canada). Gas Supply Pressure Testing Gas supply pressure for testing regulator must be at least 1" water column pressure above the manifold pressure shown on the model/serial/rating plate. Line Pressure Testing Above ½ psi Gauge (14" WCP) The range and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi (3.5 kPa). Line Pressure Testing at ½ psi Gauge (14" WCP) or Lower The range must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi (3.5 kPa). 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40

7
Flexible Metal Appliance Connector:
If local codes permit, a new CSA design-certified, 4 to 5
ft (122 to 152.4 cm) long, ½" or ¾" (1.3 or 1.9 cm) I.D.
(inside diameter), flexible metal appliance connector may
be used for connecting range to the gas supply line.
A ½" (1.3 cm) male pipe thread is needed for connection
to the female pipe threads of the inlet to the appliance
pressure regulator.
Do not kink or damage the flexible metal tubing when
moving the range.
Must include a shut-off valve:
The supply line must be equipped with a manual shut-off
valve. This valve should be located in the same room but
external to the range opening, such as an adjacent cabinet.
It should be in a location that allows ease of opening and
closing. Do not block access to shut-off valve. The valve is
for turning on or shutting off gas to the range.
A
B
C
A. Gas supply line
B. Shut-off valve “open” position
C. To range
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be
used. The inlet pressure to the regulator should be as follows
for proper operation:
Natural Gas:
Minimum pressure: 6" WCP
Maximum pressure: 14" WCP
LP Gas:
Minimum pressure: 12" WCP
Maximum pressure: 14" WCP
Contact local gas supplier if you are not sure about the inlet
pressure.
Burner Input Requirements
Input ratings shown on the model/serial/rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at
a rate of 4% for each 1,000 ft (304.8 m) above sea level (not
applicable for Canada).
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least 1"
water column pressure above the manifold pressure shown on
the model/serial/rating plate.
Line Pressure Testing Above ½ psi Gauge (14" WCP)
The range and its individual shut-off valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of ½ psi (3.5 kPa).
Line Pressure Testing at ½ psi Gauge (14" WCP) or Lower
The range must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psi (3.5 kPa).