Belkin F6C150-RKM-2U Belkin OmniGuard Rackmount UPS Software Manual - Page 58
Set the agent SNMP version
View all Belkin F6C150-RKM-2U manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 58 highlights
OmniGuardTM UPS Power Management Software Note: Above step is must, without which event message in alarm window, will come as default message of HP, "NO FORMAT DEFINED" under Event Configuration for each event. By default, HP puts "NO FORMAT DEFINED". ?? HP Openview Configuration for MIB Browser support ?? Use SNMP MIB Browser option, to check MIB Control feature for each device. Note: HP Openview, by default is sending the Get Next request, on selected node/variable in MIB Tree, say ups Input Frequency, you are trying to get the value, it actually gets next variable in the tree, and hence shows no values returned. Hence it is recommended to select parent node, and Start Query. If any configuration we find, to change this default behavior of sending Get Next request to Get Request, it will be informed to you. Set the agent SNMP version Use MSDOS prompt, after Network Node Manager is started. And give below command to set the ECM Agent SNMP version. Command: e.g. xnmsnmpconf -setV agent/Port 1 xnmsnmpconf -setV 172.5.25.27/161 1 OR xnmsnmpconf -setV SystemName/161 1 Where 172.5.25.27 is the IP Address of the PC where ECM is installed or it can be System Name of PC and Port must be 161. Configure the SNMP Configuration in HP ?? 3 Set timeout value: 2 minute (not compulsory, can be any value) ?? Set community to public in both the community fields ?? Retries: ?? Port: No need to set, it takes default 161 See below screen for ref. 58