TROUBLESHOOTING CONT. PROBLEM WARNING Line Abnormal Output Short Over Temperature Cold Start Lock Auto Restart Lock Bypass Forbidden FAULT Over Charge Charger Failure High O/P V Low O/P V Bus Fault POSSIBLE CAUSE SOLUTION Utility power is out of range for the UPS to auto-restart. Output short circuit. High temperature sensor activated protection. UPS is locked to prevent consuming battery power during shipping. "Automatic Restore" is disabled in Power Management Software (PowerPanel® Business Edition). Manual Bypass Forbidden when the LCD screen shows "Generator On" or "Converter On." Check whether voltage or frequency of input power is out of range. The connected equipment may have problems, please remove them and check again. Check the fan for operation and verify that ventilation is not obstructed. Connect UPS to utility power for first-time operation. Press "ON/OFF" button to turn UPS on. Slide the Interlock Bracket to the right. (Only for UPS models with a Maintenance Bypass Module) Battery is overcharged. Charger has failed. Output voltage is too high. Output voltage is too low. Internal DC bus voltage is too high or too low. Remove battery connector and check charger voltage. Contact CyberPower for assistance. Shut down UPS and turn o input breaker. Contact CyberPower for assistance. PRODUCT REGISTRATION CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its website (www.cyberpowersystems.com/registration) to establish that you are the Initial Customer of the Product, and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee. (Registration is not required for coverage, but note: if you do not register your purchase, you will be required to provide proof of purchase.) 5!.ƫ+3!.ƫ5/0 0/ƫ.!/!.2! ċƫ((ƫ+0$!.ƫ0 0$!ƫ,.+,!.05ƫ+"ƫ0$!%.ƫ.!/,!0%2!ƫ+3*!./ċƫ 35

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47

35
TROUBLESHOOTING CONT.
PROBLEM
POSSIBLE CAUSE
SOLUTION
WARNING
Line Abnormal
Utility power is out of range for the
UPS to auto-restart.
Check whether voltage or frequency
of input power is out of range.
Output Short
Output short circuit.
The connected equipment may have
problems, please remove them and
check again.
Over Temperature
High temperature sensor activated
protection.
Check the fan for operation and verify
that ventilation is not obstructed.
Cold Start Lock
UPS is locked to prevent consuming
battery power during shipping.
Connect UPS to utility power
for first-time operation.
Auto Restart Lock
“Automatic Restore” is disabled
in Power Management Software
(PowerPanel® Business Edition).
Press “ON/OFF“ button to turn
UPS on.
Bypass Forbidden
Manual Bypass Forbidden when the
LCD screen shows “Generator On” or
“Converter On.”
Slide the Interlock Bracket to the
right. (Only for UPS models with a
Maintenance Bypass Module)
FAULT
Over Charge
Battery is overcharged.
Remove battery connector and check
charger voltage.
Contact CyberPower for assistance.
Charger Failure
Charger has failed.
High O/P V
Output voltage is too high.
Shut down UPS and turn off input
breaker.
Contact CyberPower for assistance.
Low O/P V
Output voltage is too low.
Bus Fault
Internal DC bus voltage is too high or
too low.
CyberPower requests that you complete and return the Warranty Registration Card enclosed with the
Product or register the Product at its website (www.cyberpowersystems.com/registration) to establish that
you are the Initial Customer of the Product, and therefore entitled coverage under the Limited Warranty
and the Connected Equipment Guarantee. (Registration is not required for coverage, but note: if you do not
register your purchase, you will be required to provide proof of purchase.)
PRODUCT REGISTRATION