Table 23. Particulate contamination specifications (continued) Particulate contamination Specifications NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and non-data center environments. Corrosive dust ● Air must be free of corrosive dust. ● Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and non-data center environments. Table 24. Gaseous contamination specifications Gaseous contamination Specifications Copper coupon corrosion rate

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14

Table 23. Particulate contamination specifications (continued)
Particulate contamination
Specifications
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data center
environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center
environments.
Table 24. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013.
Silver coupon corrosion rate
<200 Å/month as defined by ANSI/ISA71.04-2013.