Fluke 1623 FE 1623 Users Manual - Page 23
Is the result of a Stakeless ground loop measurement, reliable?, Troubleshooting
View all Fluke 1623 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
Earth/Ground Tester Troubleshooting conditions (depending mainly on the soil resistivity) this may not suffice. To be sure reposition the probes and take several measurements. If the readings are approx. the same your measuring results are reliable, if not increase the probe distance. 6 Is the result of a "Stakeless ground loop measurement" reliable? Ensure that you are using the correct inducing clamp (see "Recommended Accessories")! The clamp's parameters are suited for this test method. Using an undefined clamp will render incorrect results. Ensure that the recommended minimum distance between the current clamp is kept. If the clamps are positioned too close together, the magnetic field of the inducing clamp will influence the sensing current clamp. To avoid mutual influencing, the distance between the clamps can be varied and a new test performed. If the measurement values vary only a little or not at all, the value can be regarded as reliable. 1 U ext >Limit 2 E SH H >Limit E ES S H 3 S >Limit 4 E ES S H E SH FLUKE 1623 max 50 V P2 S plus FLUKE E/C1 S/P2 H/C2 >20 m >20 m 5 Us Ug Figure 9. Troubleshooting edv008.eps 15