Fluke 1625-2 User Manual - Page 37

Clip-On Transformer Errors Correction, Measuring process

Page 37 highlights

Earth/Ground Tester Advanced Operation Measuring Earthing Impedance with 55 Hz (R*) For the calculation of short circuit currents in power supply plants, the complex earthing impedance is important. Direct measurement is possible under the following conditions: Phase angle at 50 Hz: 30 °... 60 ° inductive Auxiliary earth electrode (ohmic): Measuring process: >100 • ZE The measurement of the earthing impedance (R*) is only possible if it is activated by putting in a personalized user's code (see "Change of Setup Data with Personalized Code"). If this measuring function is activated, in every measurement of the four RE positions, the earthing impedance R* is displayed before all other measured values. Clip-On Transformer Errors Correction If the measurement of an earthing resistance by means of a clip-on transformer results in a significantly different value as if measured without the clip-on, the deviation may be due to the tolerances of the clip-on current transformer. This error can be corrected by fine tuning the clip-on transformation ratio (basic settings 1000:1). This correction applies to the transformer current range it was performed with. For other ranges a different correction may be necessary. 1. Connect a low Ohm resistor (approximately 1 Ohm - in the range you want to correct) as shown in Figure 8. Figure 8. Correcting Clip-on Transformer Errors 2. Turn central rotary switch to position " RE 3pole". edw017.eps 29

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56

Earth/Ground Tester
Advanced Operation
29
Measuring Earthing Impedance with 55 Hz (R*)
For the calculation of short circuit currents in power supply plants, the complex earthing
impedance is important. Direct measurement is possible under the following conditions:
Phase angle at 50 Hz:
30
°
... 60
°
inductive
Auxiliary earth electrode (ohmic):
>100 • Z
E
Measuring process:
The measurement of the earthing impedance (R*) is only possible if it is activated by
putting in a personalized user's code (see "Change of Setup Data with Personalized
Code"). If this measuring function is activated, in every measurement of the four R
E
positions, the earthing impedance R* is displayed before all other measured values.
Clip-On Transformer Errors Correction
If the measurement of an earthing resistance by means of a clip-on transformer results in
a significantly different value as if measured without the clip-on, the deviation may be due
to the tolerances of the clip-on current transformer. This error can be corrected by fine
tuning the clip-on transformation ratio (basic settings 1000:1). This correction applies to
the transformer current range it was performed with. For other ranges a different
correction may be necessary.
1.
Connect a low Ohm resistor (approximately 1 Ohm - in the range you want to correct)
as shown in Figure 8.
edw017.eps
Figure 8. Correcting Clip-on Transformer Errors
2.
Turn central rotary switch to position "
R
E
3pole".