To access the Logger Events Table screen, Abbreviation, Description, Symbol
View all Fluke 435-II manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 106 highlights
Fluke 434-II/435-II/437-II Users Manual Events To access the Logger Events Table screen: h F3 The Events table lists all threshold crossings of phase voltages. Thresholds according to international standards or user-definable thresholds can be used. Threshold adjustment is reached via the SETUP key and Limits. For detailed information see Chapter 24, Limits Adjustments. In Normal mode major event characteristics are listed: start time, duration, and voltage magnitude. Detail shows details of threshold crossings per phase. Wave Event shows a scope waveform around the selected event. Rms event shows the ½ cycle rms trend around the selected event. Wave event and rms event are available in Fluke 435-II and 437-II. The following Abbreviations and Symbols are used in the tables: Abbreviation Description Symbol Description CHG Rapid Voltage Change Rising voltage edge DIP Voltage Dip Falling voltage edge INT Voltage Interruption Change upwards SWL Voltage Swell Change downwards TRA Transient AMP Amp value exceeded Available function keys: F1 Switch to wave event display: this will show a scope waveform around the selected event. F2 Switch to rms event display: this will show the ½ cycle rms trend around the selected event. F3 Switch between NORMAL and DETAILED event table. F4 Return to Meter screen. 21-4 MyFlukeStore Shop for Fluke products online at: www. .com 1.877.766.5412