Frigidaire FFHP124CS1 Installation Instructions - Page 23

Microns Hg -1x10 Pa. After

Page 23 highlights

When using the vacuum pump For method of using a manifold valve, refer to its operation manual. 1. Completely tighten the flare nuts at connection point A, B, C and D. Connect valve core removal tool to the charging port, then connect vacuum hose to valve core tool. Open the schrader valve. Note: The schrader valve is inside the charging port. 2. Connect the other charge hose of manifold valve to the vacuum pump. 3. Fully open the Low Side handle of the manifold valve. 4. Operate the vacuum pump to evacuate. After starting evacuation, slightly loose the flare nut of the Low Side valve on the gas pipe side and check if the air is entering (Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus), then tighten the flare nut. The procedure verifies if there are blocks inside the tubes. 5. Make evacuation for 15 minutes or more and check that the compound meter indicates -7-3/5 x 10 Microns Hg (-1x10 Pa). After the evacuation is completed, fully close the Low Side handle of the manifold valve and stop the operation of the vacuum pump. 6. Turn the stem of the packed valve B about 45o counterclockwise for 6~7 seconds after the gas comes out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is Outdoor unit Indoor unit Manifold Valve -76cm/Hg Charge Hose Low Side High Side Charge Hose Vacuum pump a little higher than the atmospheric pressure. This procedure verifies if the refrigerant goes through the tubes correctly. 7. Close the schrader valve, then remove the valve core tool. Replace the charging port cap. 8. Fully open the packed valve stems B and A. 9. Securely tighten the cap of the packed valve. Purging the system 22

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25

Purging the system
22
When using the vacuum pump
1. Completely tighten the flare nuts at
connection point A, B, C and D.
Connect valve core removal tool
to the charging port, then connect
vacuum hose to valve core tool.
Open the schrader valve.
Note: The schrader valve is inside the
charging port.
2. Connect the other charge hose
of manifold valve to the vacuum
pump.
3. Fully open the Low Side handle of
the manifold valve.
4. Operate the vacuum pump to
evacuate. After starting evacuation,
slightly loose the flare nut of the
Low Side valve on the gas pipe
side and check if the air is entering
(Operation noise of the vacuum
pump changes and a compound
meter indicates 0 instead of
minus), then tighten the flare nut.
The procedure verifies if there are
blocks inside the tubes.
5. Make evacuation for 15 minutes or
more and check that the compound
meter indicates -7-3/5 x 10
Microns Hg (-1x10 Pa). After the
evacuation is completed, fully close
the Low Side handle of the manifold
valve and stop the operation of the
vacuum pump.
6. Turn the stem of the packed valve
B about 45
o
counterclockwise
for 6~7 seconds after the gas
comes out, then tighten the flare
nut again. Make sure the pressure
display in the pressure indicator is
For method of using a manifold valve, refer to its operation manual.
a little higher than the atmospheric
pressure. This procedure verifies
if the refrigerant goes through the
tubes correctly.
7. Close the schrader valve, then
remove the valve core tool. Replace
the charging port cap.
8. Fully open the packed valve stems B
and A.
9. Securely tighten the cap of the
packed valve.
Vacuum pump
Charge Hose
Manifold Valve
-76cm/Hg
Charge
Hose
Low Side
High Side
Outdoor unit
Indoor unit