Haier AU182AEEAA User Manual - Page 12

Electric wiring

Page 12 highlights

Installation Procedure Electric wiring 5. Electric wiring WARNING DANGER OF BODILY INJURY OR DEATH TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS. (1) Selection of size of power supply and interconnecting wires. Precautions for Electric wiring Electric wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only. The wiring method should be in line with the local wiring standard. The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should be no less 3 mm. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. If the fuse on PC board is broken please change it with the type of T3.15A/250VAC. Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.) Item Model Circuit breaker Power source Earth leakage breaker wire size Phase Switch breaker Overcurrent protector (minimum) Switch Leak (A) rated capacity (A) (mm2) breaker(A) current(mA) AU142AEEAA AU182AEEAA 1 40 AU242AGEAA 1 40 26 2.5 40 30 26 4.0 40 30 AU282AHEAA 1 40 AU28NAHEAA 3 30 AU36NAIEAA AU48NAIEAA AU52NAIEAA 3 30 AU60NAIEAA 26 6.0 40 30 20 2.5 30 30 20 4.0 30 30 (2) Wiring connection Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals. For the detailed wiring connection with the indoor units, see the corresponding indoor operation and instruction manual. 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15

5. Electric wiring
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER
SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING
LINE VOLTAGE CONNECTIONS.
(1)
Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round
type crimped terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
The wiring method should be in line with the local wiring standard.
The breaker of the air conditioner should be all-pole switch; and the distance
between its two contacts should be no less 3 mm.
If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar qualified person.
If the fuse on PC board is broken please change it with the type of T3.15A/250VAC.
Select wire sizes and circuit protection from table below. (This table shows 20 m
length wires with less than 2% voltage drop.)
WARNING
(2)
Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor
unit is supplied by
terminals.
11
Installation Procedure
Electric wiring
For the detailed wiring connection with the indoor units, see the corresponding indoor
operation and instruction manual.
30
Item
Model
Phase
3
Switch breaker
(A)
Circuit
breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
(mm
2
)
30
20
4.0
1
40
26
2.5
Switch
breaker(A)
Earth leakage breaker
Leak
current(mA)
30
40
AU36NAIEAA
AU48NAIEAA
AU52NAIEAA
AU60NAIEAA
AU28NAHEAA
AU142AEEAA
AU182AEEAA
AU282AHEAA
3
30
2.5
30
20
1
40
26
6.0
40
30
30
30
AU242AGEAA
1
40
26
4.0
40
30