Installation of Outdoor Unit, Connection, Attaching Drain-Elbow, Connection of pipes

Page 6 highlights

Outdoor unit Outdoor unit 1.Installation of Outdoor Unit Install according to Drawing for the installation of indoor and outdoor units 2.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe,and the bending radius should be 30 to 40 mm or longer. Connecting the pipe of gas side first makes working easier. The longest connecting pipe is at most 15 meters,and the max vertical distance between the indoor unit and the outdoor unit is 5 m. Half union Spanner Flare nut Torque wrench Forced fastening without careful centering may damage the threads and cause a leakage of gas. Pipe Diameter ( ) Liquid side 6.35mm(1/4") Gas side 12.7mm(1/2") Fastening torque 18N.m 50N.m Be careful that matters, such as wastes of sands, etc. shall not enter the pipe. 3.Connection Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into terminal block, then tighten the screws. Insert the cable according to terminal number in the same manner as the indoor unit. If wiring is not correct, proper operation can not be carried out and controller may be damaged. Fix the cable with a clamp. 4.Attaching Drain-Elbow If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.) 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

Outdoor unit
1.Installation of Outdoor Unit
3.Connection
4.Attaching Drain-Elbow
2.Connection of pipes
Install according to
To bend a pipe, give the roundness as large as possible not to crush the pipe
,and the bending radius
Connecting the pipe of gas side first makes working easier.
Use the same method on indoor unit. Loosen the screws on terminal block and insert the
plugs fully into
terminal block, then tighten the screws.
If wiring is not correct, proper operation can not be carried out and controller may be damaged.
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)
Drawing for the installation of indoor and outdoor units
Insert the cable according to terminal number in the same manner as the indoor unit.
Fix the cable with a clamp.
The longest connecting pipe is at most 15 meters,and the max vertical distance between the indoor
unit and the outdoor unit is 5 m.
Half union
Flare nut
Spanner
Torque wrench
6
Outdoor unit
Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.
Pipe Diameter
(
)
Liquid side
6.35mm(1/4")
Fastening torque
18N.m
Gas side
12.7mm(1/2")
50N.m
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
should be 30 to 40 mm or longer.