Haier HC60D1VAR User Manual - Page 15

Symptom, Possible Cause, Remedy

Page 15 highlights

Symptom Possible Cause Remedy Power off or loose electrical connection Make sure main switch is ON. Check and tighten all connections. Incorrect thermostat setting Set thermostat correctly No cooling Defective contactor Check for 24V at contactor coil. Open circuit breaker of blown fuses Reset or replace Defective transformer Check wiring - Replace it. Interconnecting low voltage wiring damage Replace thermostat wiring Dirty filters Clean & replace Indoor air blockage Check supply registers and return grills for blockage. Blocked outdoor coil Clear away leaves and other debris Improperly sized unit Recalculate load Insufficient Cooling Improper airflow Check - should be 400CFM/Ton Incorrect refrigerant charge Charge correctly per instruction. Air, non-condensibles or moisture in system Recover refrigerant, evacuate & recharge, add filter drier Incorrect voltage At compressor terminals, voltage must be within 10% of rating plate volts when unit is running. Water on floor or in furnace Blocked condensate drain and "P" trap Remove blockage Run or start capacitor defective Loose connection Condenser fan runs, Compressor stuck, grounded or open compressor doesn't motor winding, open internal overload Low voltage condition Low voltage condition Incorrect voltage Compressor short-cycling Defective overload protector Refrigerant undercharge Register sweat Low evaporator airflow Restriction in liquid line, High head - Low metering device or filter drier vapor pressures Flowrator piston size too small Incorrect capillary tubes Blocked outdoor coil High head - High Refrigerant overcharge or normal vapor Condenser fan not running pressures Air, non-condensibles or moisture in system Low head - High Flowrator piston size too large vapor pressures Defective compressor valves Incorrect capillary tubes Low vapor - cool Low evaporator airflow compressor - iced Operating below 65 F outdoors evaporator coil Moisture in the system High vapor Excessive load pressure Defective compressor Fluctuating head Air or non-condensibles in system and vapor pressures Pulsing noise at Air or non-condensibles in system metering device or liquid line Replace Check and tighten all connections. Wait for 2 hours for overload to reset. Replace compressor if still open. At compressor terminals, voltage must be within 10% of rating plate volts when unit is running. Add start kit components At compressor terminals, voltage must be within 10% of rating plate volts when unit is running. Replace - check for correct voltage Add refrigerant Increase blower speed or reduce restriction - replace air filter Replace defective components Change to correct size piston Change coil assembly Clear away leaves and other debris Correct system charge Repair or replace Recover refrigerant, evacuate & recharge, add filter drier Change to correct size piston Replace compressor Replace coil assembly Increase blower speed or reduce restriction - replace air filter Add low ambient kit Recover refrigerant, evacuate & recharge, add filter drier Recheck load calculation Replace Recover refrigerant, evacuate & recharge. Recover refrigerant, evacuate & recharge 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17

13
Run or start capacitor defective
Replace
Loose connection
Check and tighten all connections.
Condenser fan runs,
Compressor stuck, grounded or open
Wait for 2 hours for overload to reset.
compressor doesn't
motor winding, open internal overload
Replace compressor if still open.
Low voltage condition
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is running.
Low voltage condition
Add start kit components
Incorrect voltage
At compressor terminals, voltage must be within 10% of rating
Compressor
plate volts when unit is running.
short-cycling
Defective overload protector
Replace - check for correct voltage
Refrigerant undercharge
Add refrigerant
Register sweat
Low evaporator airflow
Increase blower speed or reduce restriction - replace air filter
Restriction in liquid line,
Replace defective components
High head - Low
metering device or filter drier
vapor pressures
Flowrator piston size too small
Change to correct size piston
Incorrect capillary tubes
Change coil assembly
Blocked outdoor coil
Clear away leaves and other debris
High head - High
Refrigerant overcharge
Correct system charge
or normal vapor
Condenser fan not running
Repair or replace
pressures
Air, non-condensibles or
Recover refrigerant, evacuate &
moisture in system
recharge, add filter drier
Low head - High
Flowrator piston size too large
Change to correct size piston
vapor pressures
Defective compressor valves
Replace compressor
Incorrect capillary tubes
Replace coil assembly
Low vapor - cool
Low evaporator airflow
Increase blower speed or reduce restriction - replace air filter
compressor - iced
Operating below 65
F outdoors
Add low ambient kit
evaporator coil
Moisture in the system
Recover refrigerant, evacuate & recharge, add filter drier
High vapor
Excessive load
Recheck load calculation
pressure
Defective compressor
Replace
Fluctuating head
Air or non-condensibles in system
Recover refrigerant, evacuate & recharge.
and vapor pressures
Pulsing noise at
Air or non-condensibles in system
Recover refrigerant, evacuate & recharge
metering device
or liquid line
Symptom
Possible Cause
Remedy
Power off or loose electrical connection
Make sure main switch is ON. Check and tighten all connections.
Incorrect thermostat setting
Set thermostat correctly
No cooling
Defective contactor
Check for 24V at contactor coil.
Open circuit breaker of blown fuses
Reset or replace
Defective transformer
Check wiring - Replace it.
Interconnecting low voltage wiring damage
Replace thermostat wiring
Dirty filters
Clean & replace
Indoor air blockage
Check supply registers and return grills for blockage.
Blocked outdoor coil
Clear away leaves and other debris
Improperly sized unit
Recalculate load
Insufficient Cooling
Improper airflow
Check - should be 400CFM/Ton
Incorrect refrigerant charge
Charge correctly per instruction.
Air, non-condensibles or moisture in system
Recover refrigerant, evacuate & recharge, add filter drier
Incorrect voltage
At compressor terminals, voltage must be within
10% of rating plate volts when unit is running.
Water on floor or in
furnace
Blocked condensate drain and "P" trap
Remove blockage