Haier HSU-09C12 User Manual - Page 6
Installation of Outdoor Unit, Connection, Connection of pipes
![]() |
View all Haier HSU-09C12 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 6 highlights
Outdoor unit Outdoor unit 1.Installation of Outdoor Unit Install according to Drawing for the installation of indoor and outdoor units 2.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe Connecting the pipe of gas side first makes working easier. The max vertical distance between the indoor unit and the outdoor unit is 5 m. Half union Flare nut Spanner Torque wrench Forced fastening without careful centering may damage the threads and cause a leakage of gas. Pipe Diameter ( ) Liquid side 6.35mm(1/4") Liquid side 9.52mm(3/8") Gas side 9.52mm(3/8") Gas side 12.7mm(1/2") Gas side 15.88mm(5/8") Fastening torque 18N.m 40N.m 40N.m 50N.m 60N.m Be careful that matters, such as wastes of sands, etc. shall not enter the pipe. 3.Connection Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into terminal block, then tighten the screws. Insert the cable according to terminal number in the same manner as the indoor unit. If wiring is not correct, proper operation can not be carried out and controller may be damaged. Fix the cable with a clamp. 4.Attaching Drain-Elbow If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.) 6