Hayward AQ-SOL-LV-TC Operation Manual - Page 14

Solar Sensor LED, on or flashing, Err on the solar temperature display, Aux Sensor LED, flashing

Page 14 highlights

On continuously indicates a probable open circuit in the "POOL" sensor or wiring. Flashing indicates a probable short circuit in the "POOL" sensor or wiring. In either case digital pool temperature display will show as "PErr". The solar heating and cooling functions will remain off until this problem is fixed, however, the recirculate freeze protection (if enabled by the jumper) will still operate properly. Use the chart on the back cover to check the "POOL" sensor with a voltmeter (you don't need to disconnect the sensor). Alternatively, you can disconnect the sensor and measure the sensor resistance. Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem. 7. "Solar Sensor" LED on or flashing "Err" on the solar temperature display: On continuously indicates a probable open circuit in the "SOLAR" sensor or wiring. Flashing indicates a probable short circuit in the "SOLAR" sensor or wiring. In either case digital pool temperature display for the "SOLAR" sensor will show as "CErr". The solar heating and cooling functions will remain off until this problem is fixed, however, the recirculate freeze protection (if enabled by the jumper) will still operate properly. Use the chart on the back cover to check the "SOLAR" sensor with a voltmeter (you don't need to disconnect the sensor). Alternatively, you can disconnect the sensor and measure the sensor resistance. Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem. 8. "Aux Sensor" LED flashing "Err" on the Aux temperature display: Flashing indicates a probable short circuit in the "AUX" sensor or wiring. The digital pool temperature display for the "AUX" sensor will show as "AErr". This error indication only occurs when the "AUX" sensor is being used for recirculate freeze protection. When the Aux sensor is shorted, the Aqua Solar will use the "SOLAR" sensor as a backup freeze sensor and turn the recirculate freeze protection on when the temperature is less than 60ºF. Use the chart on the back cover to check the "AUX" sensor with a voltmeter (you don't need to disconnect the sensor). Alternatively, you can disconnect the sensor and measure the sensor resistance. Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem. 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

11
On continuously indicates a probable open circuit in the "POOL" sensor or wiring.
Flashing indicates a probable short circuit in the "POOL" sensor or wiring.
In either
case digital pool temperature display will show as "PErr".
The solar heating and
cooling functions will remain off until this problem is fixed, however, the recirculate
freeze protection (if enabled by the jumper) will still operate properly.
Use the chart on
the back cover to check the "POOL" sensor with a voltmeter (you don't need to
disconnect the sensor).
Alternatively, you can disconnect the sensor and measure
the sensor resistance.
Replace the sensor or fix the wiring as required.
If the sensor
and wiring are both good, then the main circuit PCB may have a problem.
7.
"Solar Sensor" LED
on or flashing
"Err" on the solar temperature display:
On continuously indicates a probable open circuit in the "SOLAR" sensor or wiring.
Flashing indicates a probable short circuit in the "SOLAR" sensor or wiring.
In either
case digital pool temperature display for the "SOLAR" sensor will show as "CErr".
The solar heating and cooling functions will remain off until this problem is fixed,
however, the recirculate freeze protection (if enabled by the jumper) will still operate
properly.
Use the chart on the back cover to check the "SOLAR" sensor with a voltmeter (you
don't need to disconnect the sensor).
Alternatively, you can disconnect the sensor and
measure the sensor resistance.
Replace the sensor or fix the wiring as required.
If the
sensor and wiring are both good, then the main circuit PCB may have a problem.
8.
"Aux Sensor" LED
flashing
"Err" on the Aux temperature display:
Flashing indicates a probable short circuit in the "AUX" sensor or wiring.
The digital
pool temperature display for the "AUX" sensor will show as "AErr".
This error
indication only occurs when the "AUX" sensor is being used for recirculate freeze
protection.
When the Aux sensor is shorted, the Aqua Solar will use the "SOLAR"
sensor as a backup freeze sensor and turn the recirculate freeze protection on when
the temperature is less than 60ºF.
Use the chart on the back cover to check the "AUX" sensor with a voltmeter (you
don't need to disconnect the sensor).
Alternatively, you can disconnect the sensor and
measure the sensor resistance.
Replace the sensor or fix the wiring as required.
If the
sensor and wiring are both good, then the main circuit PCB may have a problem.