Hayward CAT 6000 CAT 6000 Owners Manual - Page 22

Change The ORP Setpoint, Change The Chlorine Setpoint, Select ORP Feed Mode, Select Chlorine Feed

Page 22 highlights

Change The ORP Setpoint The CAT 6000 is programmed with a factory default setpoint of ORP=650 mV. CAT Controllers considers this to be ideal for pool and spa applications. If drastic changes to the pool chemistry occur, in order to maintain accurate sanitizer levels relative to ORP, adjustment of the ORP setpoint may be needed. Changes in pool chemistry may include a change in the pH set point, TDS set point, or cyanuric acid level. The following steps enable the selection of a different setpoint: • From the menu, select the ORP Setpoint option using the Enter button. • Use the Up and Down buttons to select a value for the setpoint. • Push the OK button to save the setpoint. Change The Chlorine Setpoint The CAT 6000 is programmed with a factory default setpoint of Cl=3 ppm. CAT Controllers considers this to be ideal for pool and spa applications. The following steps enable the selection of a different setpoint: • From the menu, select the Cl Setpoint option using the Enter button. • Use the Up and Down buttons to select a value for the setpoint. • Push the OK button to save the setpoint. If a chlorine setpoint change is made, it is recommended that the chlorine sensor is calibrated at the new setpoint. Select ORP Feed Mode The CAT 6000 is programmed with a factory default setting to operate in automatic feed mode. Other feed mode selections include Off (disabled), and Manual On for a fixed interval up to 30 minutes after which automatic feed will resume. • From the menu, select the ORP Feed Mode option using the Enter button. • Use the Up and Down buttons to select the desired feed mode. • Push the OK button to switch to the selected mode. Select Chlorine Feed Mode The CAT 6000 is programmed with a factory default setting to operate in automatic feed mode. Other feed mode selections include Off (disabled), and Manual On for a fixed interval up to 30 minutes after which automatic feed will resume. • From the menu, select the Cl Feed Mode option using the Enter button. • Use the Up and Down buttons to select the desired feed mode. • Push the OK button to switch to the selected mode. Calibrate Chlorine Chlorine calibration is necessary to match manual water testing results, compensate for an unclean or aging chlorine sensor, and confirm proper operation of the system. Before chlorine calibration, ensure that the pH and chlorine levels of the measured water are stable at their desired setpoints. • From the menu, select the Cl Calibrate option using the Enter button. • The current chlorine measurement is displayed. 21 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
21
Change The ORP Setpoint
The CAT 6000 is programmed with a factory default setpoint of ORP=650 mV. CAT Controllers considers
this to be ideal for pool and spa applications. If drastic changes to the pool chemistry occur, in order
to maintain accurate sanitizer levels relative to ORP, adjustment of the ORP setpoint may be needed.
Changes in pool chemistry may include a change in the pH set point, TDS set point, or cyanuric acid
level. The following steps enable the selection of a different setpoint:
From the menu, select the ORP Setpoint option using the Enter button.
Use the Up and Down buttons to select a value for the setpoint.
Push the OK button to save the setpoint.
Change The Chlorine Setpoint
The CAT 6000 is programmed with a factory default setpoint of Cl=3 ppm. CAT Controllers considers
this to be ideal for pool and spa applications. The following steps enable the selection of a different
setpoint:
From the menu, select the Cl Setpoint option using the Enter button.
Use the Up and Down buttons to select a value for the setpoint.
Push the OK button to save the setpoint.
If a chlorine setpoint change is made, it is recommended that the chlorine sensor is calibrated at the
new setpoint.
Select ORP Feed Mode
The CAT 6000 is programmed with a factory default setting to operate in automatic feed mode. Other
feed mode selections include Off (disabled), and Manual On for a fixed interval up to 30 minutes after
which automatic feed will resume.
From the menu, select the ORP Feed Mode option using the Enter button.
Use the Up and Down buttons to select the desired feed mode.
Push the OK button to switch to the selected mode.
Select Chlorine Feed Mode
The CAT 6000 is programmed with a factory default setting to operate in automatic feed mode. Other
feed mode selections include Off (disabled), and Manual On for a fixed interval up to 30 minutes after
which automatic feed will resume.
From the menu, select the Cl Feed Mode option using the Enter button.
Use the Up and Down buttons to select the desired feed mode.
Push the OK button to switch to the selected mode.
Calibrate Chlorine
Chlorine calibration is necessary to match manual water testing results, compensate for an unclean
or aging chlorine sensor, and confirm proper operation of the system. Before chlorine calibration,
ensure that the pH and chlorine levels of the measured water are stable at their desired setpoints.
From the menu, select the Cl Calibrate option using the Enter button.
The current chlorine measurement is displayed.