Hayward E-Command 4 Model: ALL MODELS Operation - Page 28

Diagnostic Menu

Page 28 highlights

Diagnostic Menu To enter the Diagnostic Menu, press the "Menu" button repeatedly until the display shows "Diagnostic Menu". At this point, you can use either the "" buttons to scroll through the various menu items which are described below: If external chlorination is used Set SDaalty LaenvdeTl ime No function Wedn3e2s0d0aPy P1M0:37P Move to previous/next menu item Salt level of the pool is 3200. This is measured by the Goldline Aqua Rite or Hayward Swimpure when external chlorination is used. This display will be shown only if external chlorination is used and requires a Aqua Rite or Swimpure chlorine generator. For the chlorinator to be operating, several other things must be happening: the filter pump must be running, the flow switch must be detecting flow, the chlorinator setting must be set greater than 0%, the water temperature at the cell must be between 50ºF and 140ºF, and the salt level must be within the operating range. If any of these conditions are not met, the chlorinator diagnostic display will tell you the reason. It's possible to have more than one reason, in which case after you rectify what was displayed the first time, a second display will appear. Possible error messages are: • PCB Error • Low Salt/Amps/Minerals • High Salt/Amps/Minerals • Test Salt Level (Test Minerals) Refer to the Aqua Rite or Swimpure manual to correct error. Water Sensor Open circuit Air Sensor 94ºF Solar Sensor Short circuit No function Move to previous/next menu item No function Move to previous/next menu item No function Move to previous/next menu item If the sensor appears to operating properly, then the temperature will be displayed. If this temperature is not correct then check the placement of the sensor. If the problem is not placement related, then the sensor will, most likely, require replacement. If the display is "Open Circuit" or "Short Circuit" then check the wiring to the sensor and also make sure that the wires are secure in the terminal block in the ECOMMAND 4 main unit. Main Software Revision 2.40 Display Software Revision 3.12 Filter Bridge Software r1.00 Filter VSC Software r1.00 RF Base Software r1.20 ID:1234 No function Move to previous/next menu item No function Move to previous/next menu item No function Move to previous/next menu item No function Move to previous/next menu item No function Move to previous/next menu item Available displays depend on configuration. If you call the Hayward/Goldline Technical Service Dept. for assistance, they may ask for the software revisions of both the main unit and each of the display/keypads or other devices that are attached to the system. Note that it is possible that different display/keypads have different software revision levels. For this reason, it is advisable to check this diagnostic menu item on every display. 25

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

25
Diagnostic Menu
To enter the Diagnostic Menu, press the “Menu” button repeatedly until the display shows “Diagnostic
Menu”.
At this point, you can use either the “<” or “>” buttons to scroll through the various menu items
which are described below:
Set Day and Time
Wednesday 10:37P
Move to previous/next menu item
Salt Level
3200PPM
No function
If external chlorination is used
Salt level of the pool is 3200.
This is measured by the Goldline Aqua Rite or Hayward
Swimpure when external chlorination is used.
This display will be shown only if external chlorination is used and requires a Aqua Rite or
Swimpure chlorine generator.
For the chlorinator to be operating, several other things must
be happening: the filter pump must be running, the flow switch must be detecting flow, the
chlorinator setting must be set greater than 0%, the water temperature at the cell must be
between 50ºF and 140ºF, and the salt level must be within the operating range.
If any of these
conditions are not met, the chlorinator diagnostic display will tell you the reason.
It’s
possible to have more than one reason, in which case after you rectify what was displayed
the first time, a second display will appear.
Possible error messages are:
PCB Error
Low Salt/Amps/Minerals
High Salt/Amps/Minerals
Test Salt Level (Test Minerals)
Refer to the Aqua Rite or Swimpure manual to correct error.
Air Sensor
94ºF
Solar Sensor
Short circuit
Water Sensor
Open circuit
No function
No function
No function
Move to previous/next menu item
Move to previous/next menu item
Move to previous/next menu item
If the sensor appears to operating properly, then the temperature will be displayed.
If this
temperature is not correct then check the placement of the sensor.
If the problem is not
placement related, then the sensor will, most likely, require replacement.
If the display is
“Open Circuit” or “Short Circuit” then check the wiring to the sensor and also make sure that
the wires are secure in the terminal block in the ECOMMAND 4 main unit.
Main Software
Revision 2.40
Display Software
Revision 3.12
Filter VSC
Software r1.00
Filter Bridge
Software r1.00
RF Base Software
r1.20
ID:1234
No function
No function
No function
No function
No function
Move to previous/next menu item
Move to previous/next menu item
Move to previous/next menu item
Move to previous/next menu item
Move to previous/next menu item
Available displays depend on configuration.
If you call the Hayward/Goldline Technical
Service Dept. for assistance, they may ask for the software revisions of both the main unit
and each of the display/keypads or other devices that are attached to the system.
Note that
it is possible that different display/keypads have different software revision levels.
For this
reason, it is advisable to check this diagnostic menu item on every display.