Hayward H-Series Millivolt Na Mv Pool Heater All models English - Page 11

Indoor installation and venting, Air supply

Page 11 highlights

SECTION 3. INSTALLATION Indoor installation and venting: The following installation and service clearances must be maintained from combustible materials. Indoor Installations* Top - 36" Non-combustible floor Front - Unobstructed Vent - 6" Back - 6" Right side (Water side) - 12" Left side - 6" Figure 12 *Canada outdoor shelters Do not Install In a closet! Do not install an H210 indoor! For alcove installations, the drafthood (DHI) shall be installed so as to be in the same atmospheric pressure zone as the combustion air inlet to the pool heater. Air supply: Indoor installations and outdoor shelters must be provided with adequate combustion and ventilation air vents to assure proper heater operation. These vents must be sized according to the requirements stated in A. and B. below and must never be obstructed when heater is in operation. When air blowers are used in spa/hot tub installations, caution must be observed to insure sufficient combustion air is available to the gas heater for proper combustion. A separate blower air duct is recommended. Equipment located in confined spaces: A. All Air Supply From Inside The Building: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space (a space whose volume is not less than 50 cubic feet per 1000 BTUH). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 BTU per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches. See Figure 13. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure. B. All Air Supply From Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. 1. W hen directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. See Figure 13. 2. W hen communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. See Figure 13. 3. W hen communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour of total input rating of all equipment in the enclosure. See Figure 13. 4. W hen ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. ! NOTE: For more detailed methods of providing air for com- bustion and ventilation, refer to latest edition of the National Fuel Gas Code, ANSI Z223.1. Free Area per Btu Requirement 1 sq. in. per 1,000 btu/hr (paragraph A) 1 sq. in. per 2,000 btu/hr (paragraph B-3) 1 sq. in. per 4,000 btu/hr (paragraph B-1) 1 sq. in. per 250 btu/hr (below-ground installation) Total Input (btu/hr) 150,000 200,000 250,000 300,000 350,000 400,000 150,000 200,000 250,000 300,000 350,000 400,000 150,000 200,000 250,000 300,000 350,000 400,000 150,000 200,000 250,000 300,000 350,000 400,000 Combustion Air Free Area Required (sq. in.) 150 200 250 300 350 400 75 100 125 150 175 200 37.5 50 62.5 75 87.5 100 600 800 1000 1200 1400 1600 Ventilation Air Free Area Required (sq. in.) 150 200 250 300 350 400 75 100 125 150 175 200 37.5 50 62.5 75 87.5 100 600 800 1000 1200 1400 1600 Figure 13 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

9
SECTION 3.
INSTALLATION
Indoor installation and venting:
The following installation and service clearances must be
maintained from combustible materials.
Do not Install In a closet!
Do not install an H210 indoor!
For alcove installations, the drafthood (DHI) shall be installed
so as to be in the same atmospheric pressure zone as the com-
bustion air inlet to the pool heater.
Air supply:
Indoor installations and outdoor shelters must be provided
with adequate combustion and ventilation air vents to assure
proper heater operation. These vents must be sized according
to the requirements stated in A. and B. below and must never be
obstructed when heater is in operation.
When air blowers are used in spa/hot tub installations, cau
-
tion must be observed to insure sufficient combustion air is avail
-
able to the gas heater for proper combustion. A separate blower
air duct is recommended.
Equipment located in confined spaces:
A. All Air Supply From Inside The Building:
The confined
space shall be provided with two permanent openings com
-
municating directly with an additional room(s) of sufficient
volume so that the combined volume of all spaces meets the
criteria for an unconfined space (a space whose volume is
not less than 50 cubic feet per 1000 BTUH). The total input
of all gas utilization equipment installed in the combined
space shall be considered in making this determination. Each
opening shall have a minimum free area of 1 square inch per
1,000 BTU per hour of the total input rating of all gas utiliza
-
tion equipment in the confined space, but not less than 100
square inches. See Figure 13. One opening shall be within
12 inches of the top and one within 12 inches of the bottom of
the enclosure.
B. All Air Supply From Outdoors:
The confined space shall
be provided with two permanent openings, one commenc
-
ing within 12 inches of the top and one commencing within
12 inches of the bottom of the enclosure. The openings shall
communicate directly, or by ducts, with the outdoors or spac-
es (crawl or attic) that freely communicate with the outdoors.
1.
When directly communicating with the outdoors, each opening
shall have a minimum free area of 1 square inch per 4,000
BTU per hour of total input rating of all equipment in the enclo
-
sure. See Figure 13.
2.
When communicating with the outdoors through vertical ducts,
each opening shall have a minimum free area of 1 square
inch per 4,000 BTU per hour of total input rating of all equip
-
ment in the enclosure. See Figure 13.
3.
When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch per 2,000 BTU per hour of total input rating of all
equipment in the enclosure. See Figure 13.
4.
When ducts are used, they shall be of the same cross-sec
-
tional area as the free area of the openings to which they con
-
nect. The minimum dimension of rectangular air ducts shall be
not less than 3 inches.
!
NOTE:
For more detailed methods of providing air for com
-
bustion and ventilation, refer to latest edition of the National Fuel
Gas Code, ANSI Z223.1.
Figure 13
Figure 12
Indoor Installations*
Top - 36”
Non-combustible floor
Front - Unobstructed
Vent - 6”
Back - 6”
Right side (Water side) - 12”
Left side - 6”
*Canada outdoor shelters
Free Area per Btu
Requirement
Total Input
(btu/hr)
Combustion Air
Free Area
Required
(sq. in.)
Ventilation Air
Free Area
Required
(sq. in.)
1 sq. in. per
1,000 btu/hr
(paragraph A)
150,000
150
150
200,000
200
200
250,000
250
250
300,000
300
300
350,000
350
350
400,000
400
400
1 sq. in. per
2,000 btu/hr
(paragraph B-3)
150,000
75
75
200,000
100
100
250,000
125
125
300,000
150
150
350,000
175
175
400,000
200
200
1 sq. in. per
4,000 btu/hr
(paragraph B-1)
150,000
37.5
37.5
200,000
50
50
250,000
62.5
62.5
300,000
75
75
350,000
87.5
87.5
400,000
100
100
1 sq. in. per
250 btu/hr
(below-ground
installation)
150,000
600
600
200,000
800
800
250,000
1000
1000
300,000
1200
1200
350,000
1400
1400
400,000
1600
1600