Hayward H-Series Millivolt Na Mv Pool Heater All models English - Page 37

Hayward H-Series Millivolt Na Mv Pool Heater Manual

Page 37 highlights

SECTION 7. TROUBLESHOOTING Troubleshooting Chart: This chart may be used as a quick reference guide for maintenance and service problems. FOR QUALIFIED SERVICE PERSONNEL ONLY. PROBLEM POSSIBLE CAUSES REMEDY HEATER WILL NOT FIRE UP See Troubleshooting Procedure That Pertains To Your Heater, (Millivolt or Electronic Ignition). Time Clock Set Wrong. Reset Clock. Filter Is Dirty. HEATER CYCLING ON AND OFF CON- TINUOUSLY. External By-Pass Out Of Adjustment, (Where Used). Clean Filter. Adjust By-Pass. Pressure Switch Out Of Adjustment. Adjust Pressure Switch. High Water Flow Rates (Above 125 GPM). Reduce Flow Rate By Adding A Manual By-Pass Valve. Internal By-Pass Stuck Open. Check For Excessive Hardness Or Acidity That May Have Damaged Valve. Repair Or Replace. SOOTING OF THE HEAT EXCHANGER. Lack Of Air For Combustion. Low Fuel Volume. Provide Adequate Air. See Venting Installation. Correct With Proper Gas Line Sizing. Improper Venting. Provide By Proper Venting. See Section II. Burner Inlet Throat Blocked. High Pressure/Low Clean Burners Adjust Gas Pressure. Pressure. Collapsed Combustion Chamber. Replace Combustion Chamber. Low Gas Pressure. Increase Pressure. PILOT OUTAGE (MILLIVOLT ONLY) Restricted Gas Flow. Clean Pilot Orifice Or Tubing. Weak Thermopile. Replace Thermopile. JACKET SURFACE TEMPERATURES EXCESSIVE. Broken Refactory. Replace Refactory. By-Pass Valve Stuck Open. Inspect By-Pass Movement And Repair. LIME SCALE. Thermal Control Valve Not Working. Water Chemistry Out Of Balance. Check For Movement. Replace If Not Movement. See Section On Pool Water Chemistry. Unnecessary External Manual By-Pass Installed Close Manual By-Pass Valve And Re- Or Out Of Adjustment. move Or Adjust Properly. See Section on By-Pass Valve. Gas Line Too Small. Check Gas Pipe Size in Figure 20. Heater Too Small. Check Sizing Chart. Install Larger Heater If Necessary. HEATER WILL NOT BRING POOL TO DESIRED TEMPERATURE. Time Clock Is Set Incorrectly. Filter Not Cleaned Often Enough. Reset Time Clock. Clean Filter More Frequently. Thermostat Out Of Adjustment Or Defective. Test Thermostat. Replace If Necessary. Pressure Switch Inoperative. Test Pressure Switch. Replace If Necessary. LEAKING HEAT EXCHANGER. Overly Acid Water Or Freeze-Up. Replace Heat Exchanger And Maintain Water Chemistry Properly. LEAKING AT WELL. Overly Acid Water Or Freeze-Up. Replace Well. Maintain Water Chemistry. LEAKING AT UNION NUT CONNECTIONS. OVERHEATED O-RINGS (BRITTLE). Heater Continues To Run After Pump Shuts Off. Refactory Damage. See Pressure Switch Adjustment. Replace leaking O-Rings. Replace Refactory. 35

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

35
SECTION 7.
TROUBLESHOOTING
Troubleshooting Chart:
PROBLEM
POSSIBLE CAUSES
REMEDY
HEATER WILL NOT FIRE UP
See Troubleshooting Procedure That
Pertains To Your Heater, (Millivolt or
Electronic Ignition).
HEATER CYCLING ON AND OFF CON
-
TINUOUSLY.
Time Clock Set Wrong.
Reset Clock.
Filter Is Dirty.
Clean Filter.
External By-Pass Out Of Adjustment, (Where
Used).
Adjust By-Pass.
Pressure Switch Out Of Adjustment.
Adjust Pressure Switch.
SOOTING OF THE HEAT
EXCHANGER.
High Water Flow Rates (Above 125 GPM).
Reduce Flow Rate By Adding A Manual
By-Pass Valve.
Internal By-Pass Stuck Open.
Check For Excessive Hardness Or
Acidity That May Have Damaged Valve.
Repair Or Replace.
Lack Of Air For Combustion.
Provide Adequate Air.
See Venting
Installation.
Low Fuel Volume.
Correct With Proper Gas Line Sizing.
Improper Venting.
Provide By Proper Venting.
See Section
II.
Burner Inlet Throat Blocked.
High Pressure/Low
Pressure.
Clean Burners Adjust Gas Pressure.
Collapsed Combustion Chamber.
Replace Combustion Chamber.
PILOT OUTAGE (MILLIVOLT ONLY)
Low Gas Pressure.
Increase Pressure.
Restricted Gas Flow.
Clean Pilot Oriļ¬ce Or Tubing.
Weak Thermopile.
Replace Thermopile.
JACKET SURFACE
TEMPERATURES EXCESSIVE.
Broken Refactory.
Replace Refactory.
LIME SCALE.
By-Pass Valve Stuck Open.
Inspect By-Pass Movement And Repair.
Thermal Control Valve Not Working.
Check For Movement.
Replace If Not
Movement.
Water Chemistry Out Of Balance.
See Section On Pool Water Chemistry.
Unnecessary External Manual By-Pass Installed
Or Out Of Adjustment.
Close Manual By-Pass Valve And Re
-
move Or Adjust Properly.
See Section
on By-Pass Valve.
HEATER WILL NOT BRING POOL
TO DESIRED TEMPERATURE.
Gas Line Too Small.
Check Gas Pipe Size in Figure 20.
Heater Too Small.
Check Sizing Chart.
Install Larger
Heater If Necessary.
Time Clock Is Set Incorrectly.
Reset Time Clock.
Filter Not Cleaned Often Enough.
Clean Filter More Frequently.
Thermostat Out Of Adjustment Or Defective.
Test Thermostat.
Replace If Necessary.
Pressure Switch Inoperative.
Test Pressure Switch.
Replace If Neces-
sary.
LEAKING HEAT EXCHANGER.
Overly Acid Water Or Freeze-Up.
Replace Heat Exchanger And Maintain
Water Chemistry Properly.
LEAKING AT WELL.
Overly Acid Water Or Freeze-Up.
Replace Well.
Maintain Water Chemistry.
LEAKING AT UNION NUT
CONNECTIONS.
OVERHEATED
O-RINGS (BRITTLE).
Heater Continues To Run After Pump Shuts Off.
See Pressure Switch Adjustment.
Re
-
place leaking O-Rings.
Refactory Damage.
Replace Refactory.
This chart may be used as a quick reference guide for maintenance and service problems.
FOR QUALIFIED SERVICE PERSONNEL ONLY.