Hayward H-Series Models: ABG1001 H100ID1 - Page 3

I. General Information - heater

Page 3 highlights

Section I. General Information Important notice: The instructions herein are intended for the use of a qualified technician, specifically trained and experienced in the installation of this type of heating equipment. Some states or provinces require that installation and service personnel performing the installation be licensed. If this is the case in the state or province where heater is located, the contractor must be properly licensed. :$51,1*)DLOXUHWRFRPSO\ZLWKWKHDSSOLDQFH installation instructions and service instructions in this PDQXDOPD\UHVXOWLQHTXLSPHQWGDPDJHILUHDVSK\[LDWLRQRUFDUERQPRQR[LGHSRLVRQLQJ([SRVXUHWRSURGXFWVRILQFRPSOHWHFRPEXVWLRQ FDUERQPRQR[LGH FDQ cause cancer and birth defects or other reproductive harm. Conformance with codes: The heater shall be installed in accordance with all local and state codes. The heater installation must conform to WKHODWHVWHGLWLRQRIWKH1DWLRQDO)XHO*DV&RGH$PHULFDQ 1DWLRQDO6WDQGDUG $16, =DQGZLWKWKHUHTXLUHPHQWV RIWKHDXWKRULW\KDYLQJMXULVGLFWLRQ'HVLJQ&HUWLILFDWLRQLQ WKH8QLWHG6WDWHVLVLQFRPSOLDQFHZLWK$16,= ODWHVW HGLWLRQ  )RU&DQDGLDQLQVWDOODWLRQVWKHKHDWHUPXVWEHLQVWDOOHG LQDFFRUGDQFHZLWKVWDQGDUGV&$1&*$%DQG 167$//$7,21&2'(6)25*$6%851,1* $33/,$1&(6$1'(48,30(17and/or local codes, DQGLIDSSOLFDEOH6WDQGDUG&6 1$',$1 (/(&75,&$/&2'(3DUW Location of heater: /RFDWHWKHKHDWHULQDQDUHDZKHUHDOHDNLQJKHDW H[FKDQJHURUFRQQHFWLRQOHDNZLOOQRWUHVXOWLQGDPDJHWR the area adjacent to the heater or structure. This heater must be installed at least five feet from WKHZDOORIDQDERYHJURXQGSRRO The heater shall not be installed with the top of the vent DVVHPEO\ZLWKLQIHHWEHORZRUWRHLWKHUVLGHRIDQ\RSHQing into the building. Outdoor installation only: The following installation and service clearances must be maintained from surfaces to provide adequate air flow to the heater. Outdoor Installations Top - Unobstructed Front - 10 inches Back - 10 inches Right side - 10 inches Left side - 10 inches Bottom - Combustible floor Figure 1 $Q$*$&HUWLILHGPDLQJDVYDOYHVKXWRIIPXVWEH LQVWDOOHGRXWVLGHRIWKHFDELQHWDQGZLWKLQIHHWRIWKHKHDWer. Gas shutoff valve must have an inside diameter large enough to supply the proper amount of gas volume to the heater. 127('RQRWXVHIOH[LEOHDSSOLDQFHFRQQHFWRUVRQ DQ\JDVFRQQHFWLRQVXQOHVVWKHFRQQHFWRULV$*$ DSSURYHGIRURXWGRRU,QVWDOODWLRQ,VPDUNHGZLWKWKH %78+FDSDFLW\ ZKLFKPXVWEHHTXDOWRRUJUHDWHUWKDQ %78+ DQGWKHW\SHRIJDV 1DWXUDORU/3 WREH used. Propane Gas: $OO3URSDQHJDVWDQNVPXVWEHORFDWHGRXWGRRUVDZD\ from the pool and in accordance with the standard for storDJHDQGKDQGOLQJRISURSDQHJDV$16,1)3$ ODWHVW HGLWLRQ DQGDSSOLFDEOHORFDOFRGHV,ISURSDQHJDVWDQNLV installed underground, the discharge of the regulator vent must be above the highest probable water level. 3URSDQHWDQNVPXVWKDYHVXIILFLHQWFDSDFLW\WRSURYLGH adequate vaporization for the full capacity of the equipment DWWKHORZHVWH[SHFWHGWHPSHUDWXUHV&RQVXOWDSURSDQH company expert for correct sizing. Water piping: This heater is designed for use with pool and spa/hot tub water only, as furnished by municipal water distribution systems. The warranty does not cover heater use with mineral water, sea, salt, or other non-potable waters. Do not install any restriction in the water pipe between a heater outlet and the pool/spa with the exception of a threeZD\VZLWFKLQJYDOYHDQGDVVRFLDWHGFKHFNYDOYH%ORFNDJH of water flow from heater return to pool may result in fire or explosion causing property damage, personal injury, or loss of life. Plumbing connections: Water flow rate to the pool must be between 20 and 70 gpm. If flow rate exceeds 70 gpm an external by-pass valve must be installed. Figure 2 shows a typical heater installation. Electrical system: 7KLVKHDWHULVHTXLSSHGZLWKDVWDQGDUGSURQJYROW cordset. The plug must be inserted into a GFI protected, ZDWHUWLJKWRXWGRRUUHFHSWDFOHUDWHGIRUDWOHDVWDPSV The heater must be electrically grounded and bonded in accordance with local codes, or in the absence of local FRGHVZLWKWKH1DWLRQDO(OHFWULFDO&RGH$16,$)3$ If the heater must be hard wired, open the junction box and disconnect the cord. Remove the cord and strain relief and wire the heater in accordance with local codes or the 1DWLRQDO(OHFWULFDO&RGH The ignition system used to light the burners is a direct VSDUNV\VWHPZKLFKUHTXLUHVYROW$&FXUUHQWDVGRHV the blower motor. The system amp draw is 2 amps. It is strongly recommended that the heater be supplied with a constant power source. If remote operation is required, the heater should be controlled through the thermostat only. Installation above or below water level: This heater is supplied with a pressure switch factory set DWSVL,IWKHKHDWHUGRHVQRWRSHUDWHDQGWKHSUHVVXUH switch is at fault, the following procedure is recommended to adjust the switch: 3

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10

Important notice:
The instructions herein are intended for the use of a
qualified technician, specifically trained and experienced
in the installation of this type of heating equipment. Some
states or provinces require that installation and service per-
sonnel performing the installation be licensed. If this is the
case in the state or province where heater is located, the
contractor must be properly licensed.
installation instructions and service instructions in this
-
-
cause cancer and birth defects or other reproductive
harm.
Conformance with codes:
The heater shall be installed in accordance with all local
and state codes. The heater installation must conform to
and/or local codes,
Location of heater:
the area adjacent to the heater or structure.
This heater must be installed at least five feet from
The heater shall not be installed with the top of the vent
-
ing into the building.
Outdoor installation only:
The following installation and service clearances must be
maintained from surfaces to provide adequate air flow to the
heater.
Figure 1
-
er. Gas shutoff valve must have an inside diameter large
enough to supply the proper amount of gas volume to the
heater.
used.
Propane Gas:
from the pool and in accordance with the standard for stor-
installed underground, the discharge of the regulator vent
must be above the highest probable water level.
adequate vaporization for the full capacity of the equipment
company expert for correct sizing.
Water piping:
This heater is designed for use with pool and spa/hot
tub water only, as furnished by municipal water distribution
systems. The warranty does not cover heater use with min-
eral water, sea, salt, or other non-potable waters.
Do not install any restriction in the water pipe between a
heater outlet and the pool/spa with the exception of a three-
of water flow from heater return to pool may result in fire or
explosion causing property damage, personal injury, or loss
of life.
Plumbing connections:
Water flow rate to the pool must be between 20 and
7
0
gpm. If flow rate exceeds
7
0 gpm an external by-pass valve
must be installed. Figure 2 shows a typical heater installa-
tion.
Electrical system:
cordset. The plug must be inserted into a GFI protected,
The heater must be electrically grounded and bonded in
accordance with local codes, or in the absence of local
If the heater must be hard wired, open the junction box
and disconnect the cord. Remove the cord and strain relief
and wire the heater in accordance with local codes or the
The ignition system used to light the burners is a direct
the blower motor. The system amp draw is 2 amps.
It is strongly recommended that the heater be sup-
plied with a constant power source. If remote operation is
required, the heater should be controlled through the ther-
mostat only.
Installation above or below water level:
This heater is supplied with a pressure switch factory set
switch is at fault, the following procedure is recommended
to adjust the switch:
Section I. General Information
3
Outdoor Inst
a
ll
a
tions
Top - Unobstructed
Ri
g
ht side
- 10 inches
Front - 10 inches
Le
f
t side - 10 inches
B
a
ck - 10 inches
Botto
m
- Co
m
bustible
f
loor