Hayward High Flow High Flow Suction Outlet Manual - Page 3

Recommended System Specifications - pump

Page 3 highlights

Page 3 of 8 DUAL SUBMERGED SUCTION OUTLET RECOMMENDED SYSTEM SPECIFICATIONS: ACCEPTABLE PIPE SIZE FOR MAXIMUM RECOMMENDED SYSTEM FLOW RATE PER APSP-7 (6 FT/SEC IN THE BRANCH LINE) Pipe Flow rate Pipe Flow rate Size GPM Size GPM [mm] [Liter/Min] [mm] [Liter/Min] 2 ½" 90 4" 238 [75] [340] [100] [900] 3" 138 6" 540 [90] [522] [90] [2040] CHART 1 ISSQUAREHF REV C WG1031BHF Suction Outlet Cover (Replacement sold as a WGX1031BHF) is rated for 224 GPM Wall Mounted or 264 GPM Floor Mounted for single or multiple suction outlet use. (9" x 9") WG1032BHF Suction Outlet Cover (Replacement sold as a WGX1032BHF) is rated for 308 GPM Wall Mounted or 515 GPM Floor Mounted for single or multiple suction outlet use. (12" x 12") WG1033BHF Suction Outlet Cover (Replacement sold as a WGX1033BHF) is rated for 732 GPM Wall Mounted or 812 GPM Floor Mounted for single or multiple suction outlet use (This is a package of four 9" x 9" covers and frames) (18" x 18") In the event of one suction outlet being blocked, the remaining suction outlets serving that system shall have a flow rating capable of the full flow of the pump(s) for the specific suction system. Example: In the System shown in Diagram 1, two (2) 12" Square (WG1032HFPAK2) suction outlet covers are selected and mounted on the floor. These covers are individually rated for 515 GPM. For a desired flow of 130 GPM, a minimum pipe size from Chart 1 is selected at 3". At the desired flow of 130 GPM one cover could be partially blocked and the other suction outlet flow would be below the rated 515 GPM of the remaining suction outlet. Since there are two outlets flowing in normal operation, and the allowable velocity in the branch piping is only 3ft/sec with both outlets flowing, the branch piping would require 3" pipe size. Example: In the System shown in Diagram 2, two (2) 12" Square (WG1032HFPAK2) suction outlet covers are selected and mounted, on one the floor and the other on the wall. These covers are individually rated for 515 GPM on the floor and 308 GPM when wall mounted. For a desired flow of 110 GPM, a minimum pipe size from Chart 1 is selected at 3". At the desired flow of 110 GPM one cover could be partially blocked and the other suction outlet flow would be below the rated 308 GPM of the remaining suction outlet. Since there are two outlets flowing in normal operation, and the allowable velocity in the branch piping is only 3ft/sec with both outlets flowing, the branch piping would require 3" pipe size. Minimum distance 3 feet (Pipe Centerlines) Dual Outlets on Different Planes (Elevation or Plan View) Branch piping Branch piping System piping System piping Diagram 1 Diagram 2

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

Page 3 of 8
DUAL SUBMERGED SUCTION OUTLET
ISSQUAREHF
REV C
RECOMMENDED SYSTEM SPECIFICATIONS
:
W
G1031BHF Suction Outlet Cover (Replacement sold as a WGX1031BHF) is rated for 224 GPM Wall Mounted or
264 GPM Floor Mounted for single or multiple suction outlet use. (9” x 9”)
WG1032BHF Suction Outlet Cover (Replacement sold as a WGX1032BHF) is rated for 308 GPM Wall Mounted or
515 GPM Floor Mounted for single or multiple suction outlet use. (12” x 12”)
WG1033BHF Suction Outlet Cover (Replacement sold as a WGX1033BHF) is rated for 732 GPM Wall Mounted or
812 GPM Floor Mounted for single or multiple suction outlet use (This is a package of four 9” x 9” covers and
frames) (18” x 18”)
In the event of one suction outlet being blocked, the remaining suction outlets serving that system shall have a flow rating
capable of the full flow of the pump(s) for the specific suction system.
Example:
In the System shown in
Diagram 1
, two (2) 12” Square (WG1032HFPAK2) suction outlet covers are selected
and mounted on the floor.
These covers are individually rated for 515 GPM.
For a desired flow of 130 GPM, a
minimum pipe size from
Chart 1
is selected at 3”.
At the desired flow of 130 GPM one cover could be partially
blocked and the other suction outlet flow would be below the rated 515 GPM of the remaining suction outlet.
Since
there are two outlets flowing in normal operation, and the allowable velocity in the branch piping is only 3ft/sec with
both outlets flowing, the branch piping would require 3” pipe size.
Example:
In the System shown in
Diagram 2
, two (2) 12” Square (WG1032HFPAK2) suction outlet covers are selected
and mounted, on one the floor and the other on the wall.
These covers are individually rated for 515 GPM on the
floor and 308 GPM when wall mounted.
For a desired flow of 110 GPM, a minimum pipe size from
Chart 1
is
selected at 3”.
At the desired flow of 110 GPM one cover could be partially blocked and the other suction outlet flow
would be below the rated 308 GPM of the remaining suction outlet.
Since there are two outlets flowing in normal
operation, and the allowable velocity in the branch piping is only 3ft/sec with both outlets flowing, the branch piping
would require 3” pipe size.
ACCEPTABLE PIPE SIZE FOR
MAXIMUM RECOMMENDED
SYSTEM FLOW RATE PER APSP-7
(6 FT/SEC IN THE BRANCH LINE)
Pipe
Size
[mm]
Flow rate
GPM
[Liter/Min]
Pipe
Size
[mm]
Flow rate
GPM
[Liter/Min]
2 ½”
[75]
90
[340]
4”
[100]
238
[900]
3”
[90]
138
[522]
6”
[90]
540
[2040]
CHART 1
Diagram 1
Diagram 2
Minimum distance 3 feet
(Pipe Centerlines)
Dual Outlets on Different Planes
(Elevation or Plan View)
Branch piping
System piping
Branch piping
System piping