Hayward Max-Flo XL Max-Flo XL Manual - Page 8
Electrical, WARNING, Electrical Specs, Voltage, Grounding and Bonding - 1 5 hp sp2310x15
View all Hayward Max-Flo XL manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 8 highlights
3.5. Electrical WARNING - All electrical wiring MUST conform to local codes, regulations, and the National Electric Code (NEC). WARNING - Ground and bond pump before connecting to electrical power supply. Failure to ground and bond pump can cause serious or fatal electrical shock hazard. Do NOT ground to a gas supply line. To avoid dangerous or fatal electrical shock, turn OFF power to pump before working on electrical connections. Fire Hazard match supply voltage to pump nameplate voltage. Insure that the electrical supply available agrees with the pump's voltage, phase, and cycle, and that the wire size is adequate for the amps rating and distance from the power source. Use copper conductors only. 3.6. Electrical Specs Use copper conductors only. For indoor & outdoor use. PUMP MODEL SP2305X7 SP2305X7EE SP2305X7EESP SP2307X10 SP2307X102 SP2310X15 SP2310X152 SP2315X20 SP2315X202 TOTAL HP 0.95 0.95 0.95 1.25 1.25 / 0.20 1.65 1.65 / 0.27 2.10 2.20 / 0.36 RATED HP 0.75 0.75 0.75 1.00 1.00 / 0.16 1.50 1.50 / 0.25 2.00 2.00 / 0.33 VOLTAGE 115 / 208-230 115 / 208-230 115 / 208-230 115 / 208-230 230 115 / 208-230 230 115 / 208-230 230 AMPS 10.0 / 6.0-5.0 9.2 / 4.7-4.6 9.2 / 4.7-4.6 13.3 / 6.9-6.8 6.1 / 2.1 16.5 / 9.2-8.5 7.7 / 2.8 17.4 / 10.6-8.8 10.0 / 3.0 3.7. Voltage Voltage at pump MUST NOT be more than 10% above or below nameplate rated voltage, or components may overheat, causing overload tripping and reduced component life. If voltage is less than 90% or more than 110% of rated voltage when pump is running at full load, consult the power company. 3.8. Grounding and Bonding 1. Install, ground, bond, and wire pump in accordance with local or national electrical code requirements. 2. Permanently ground pump. Use green ground terminal provided under access plate; use size and type wire required by code. Connect ground terminal to electrical service ground. 3. Bond pump to pool structure. Bonding will connect all metal parts within and around the pool with a continuous wire. Bonding reduces the risk of a current passing between bonded metal objects, which could potentially cause electrical shock if grounded or shorted. Reference NEC codes for all wiring standards including, but not limited to, grounding, bonding and general wiring procedures. 4. Use a solid copper conductor, size 8 or larger. Run wire from external bonding lug to reinforcing rod or mesh. Connect a No. 8 AWG (8.4 mm2) [No. 6 AWG (13.3 mm2) for Canada] solid copper bonding wire to the pressure wire connector provided on the motor housing and to all metal parts of swimming pool, spa, or hot tub, and to all electrical equipment, metal piping (except gas piping), and conduit within 5 ft. (1.5 m) of inside walls of swimming pool, spa, or hot tub. Page 8 of 20 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Max-Flo XL Pump IS2300 Rev-A1