Hayward Summit In Ground Heat Pump 65 000 BTUs Owners Manual - Page 12
Using an External Controller
View all Hayward Summit In Ground Heat Pump 65 000 BTUs manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 12 highlights
Using an External Controller To connect the electronic board in order to control it remotely, use the P_S terminals on the right side of the board. Next, access the P_S menu and select the desired mode. In internal mode, POOL or SPA mode can be adjusted by using this menu. In external mode, a normally open contact puts the board in POOL mode and a closed contact puts the board in SPA mode. Therefore, a board set to OFF in POOL mode and to 80 degrees in SPA mode can be controlled with an external switch to heat up to 80 degrees. Internal mode: Use the P_S mode on the main menu External mode: • Open contact = POOL mode • Closed contact = SPA mode Control using a switch To control the board using an external switch, follow these steps : • Turn on the heat pump. • Set POOL mode to OFF. • Set SPA mode to the desired temperature. • Access the setup menu. • Select mode E (external) on the P_S menu. • Run two J7 (P_S) terminal wires from the HPEC-003 board to the NO switch terminals (see FIG. 4). • You can now control the operating mode by turning off the switch (open = POOL, closed = SPA.) Fig. 4 External switch Pool (open) Spa (closed) 10 OWNER'S MANUAL