HP Integrity rx6600 Site Preparation Guide, Third Edition - HP Integrity rx660 - Page 10

Grounding, Electrical Specifications, System Power Specifications

Page 10 highlights

Table 1-2 Rack- or Pedestal-Installed Server Dimensions and Values Dimension Server weight (loaded product weight range estimate) Rack Rack dimensions (depth x width x height) Rack weight Rack unit Pedestal Pedestal dimensions (depth x width x height) Pedestal weight Minimum standalone configuration Maximum standalone configuration Value 53.4 - 68 kg (120-150 lbs.) 69.6 cm (27.4 in) x 44 cm (17.32 in) x 30.58 cm (12.04 in) Max: 68.04 kg (150 lbs) Server takes up 7U in the rack 69.3 cm (27.3 in) x 48.9 cm (19.3 in) x 42.2 cm (16.7 in) Max: 15.5 kg. (34 lbs.) 69.9 kg. (154 lbs.) 83.5 kg. (184 lbs.) Grounding The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets. Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing conductor is to be connected from the unit to the building installation earth or, if supplied by a separately derived system, at the supply transformer or motor-generator set grounding point. Electrical Specifications This section provides electrical specifications for the server. System Power Specifications Available power (output) is the maximum dc power that the power supply can supply to the system. Maximum input power is what the power supply requires from the ac line to deliver that maximum dc output (given worst case efficiency and max loading). Maximum input current is the worst case/highest current given the lowest input voltage and the maximum input power. Table 1-3 lists the system power specifications. Table 1-3 System Power Specifications Parameter ac Voltage Maximum dc Output Power Maximum System Input Current Input frequency Max. per PCI/PCI-X/PCI-E Sockets Maximum Configuration2 Rating 200-240 V ac 1600 W 9 A1 47 to 63 Hz 25 W per socket 1633 W (5575 BTU) 10 System Specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15

Table 1-2 Rack- or Pedestal-Installed Server Dimensions and Values
Value
Dimension
53.4 - 68 kg (120-150 lbs.)
Server weight (loaded product weight range
estimate)
Rack
69.6 cm (27.4 in) x 44 cm (17.32 in) x 30.58 cm (12.04 in)
Rack dimensions (depth x width x height)
Max: 68.04 kg (150 lbs)
Rack weight
Server takes up 7U in the rack
Rack unit
Pedestal
69.3 cm (27.3 in) x 48.9 cm (19.3 in) x 42.2 cm (16.7 in)
Pedestal dimensions (depth x width x height)
Max: 15.5 kg. (34 lbs.)
Pedestal weight
69.9 kg. (154 lbs.)
Minimum standalone configuration
83.5 kg. (184 lbs.)
Maximum standalone configuration
Grounding
The site building shall provide a safety ground/protective earth for each AC service entrance to
all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor is to be connected from the unit to the building installation earth
or, if supplied by a separately derived system, at the supply transformer or motor-generator set
grounding point.
Electrical Specifications
This section provides electrical specifications for the server.
System Power Specifications
Available power (output) is the maximum dc power that the power supply can supply to the
system.
Maximum input power is what the power supply requires from the ac line to deliver that
maximum dc output (given worst case efficiency and max loading).
Maximum input current is the worst case/highest current given the lowest input voltage and the
maximum input power.
Table 1-3
lists the system power specifications.
Table 1-3 System Power Specifications
Rating
Parameter
200-240 V ac
ac Voltage
1600 W
Maximum dc Output Power
9A
1
Maximum System Input Current
47 to 63 Hz
Input frequency
25 W per socket
Max. per PCI/PCI-X/PCI-E Sockets
1633 W (5575 BTU)
Maximum Configuration
2
10
System Specifications