HP LH4r HP Netserver LC 2000r Rack Cabling Reference Guide - Page 45
L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 45 highlights
Chapter 3 Procedure for Connecting and Routing Cables to the LC 2000r Table 3-2. 208 VAC Components Component1 Model 208 VAC PDU HP NetServer LC 2000r E7671A or E7672A D8515A, 533 MHz, 128 MB D8520A, 600 MHz, 128 MB D8525A, 667 MHz, 128 MB Power (VA) N/A Power (W) N/A Current (A)2 max 16 516 506 2.5 HP NetServer Rack Storage/12 is D5989A 522 512 2.6 Mass Storage Rack Storage/12FC is D5991A Unit HP Console Switch J1497B 42 29 0.2 Note 1 More ratings are listed in Table 2-8. For a full list of power ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site. Note 2 Indicated current ratings are for use in selecting PDU and UPS components and may not reflect actual measured amounts. Description of the Recommended 208 VAC Configuration Figure 3-4 shows a UPS connected to the power mains through a captive cord terminated with an L6-20P plug. The UPS has five receptacles for use in the rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC 320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13 receptacles. A second PDU (E7670A) is available, which can be daisy-chained to the 16-amp unit, providing ten more C-13 receptacles. 41