HP LH4r HP Netserver LH 4 Rack Storage/12FC Cluster Config Guide for Windows - Page 1

HP LH4r - NetServer - 256 MB RAM Manual

Page 1 highlights

HP NetServer LH4 with HP Rack Storage/12FC & HP Rack Storage/12 Cluster Configuration Guide 7 September 2000 (see Versions at the end of this document) Introduction This document defines the supported HP NetServer LH4 configurations using the HP Rack Storage/12FC and Microsoft Cluster Server and one or two HP Rack Storage/12's. These configurations minimize single points of failure (SPOF) and provide extended availability. The specific configuration certified and supported by both Hewlett-Packard and Microsoft is defined, as are other guidelines to assist you in configuring your clustered NetServers. This guide is prescriptive; it describes the configurations supported by HP. Any deviance to these configurations can result in an inoperative cluster or an operating cluster with degraded performance, hidden SPOFs, etc., and therefore will not be supported by HP. What's Defined in a Cluster • Cluster • SPUs • Local and Shared Storage • Intra-cluster and Client LANs • Shared Storage Cabling Cluster Type of SPUs Number of nodes Shared Storage LANs: Client LAN Intra-cluster (Heartbeat) LAN Power source System software: Navigator version HP NetServer LH4 Each node must be the same model SPU, but may have different clock speeds, main memory sizes, cache sizes, and number of CPUs (2, 3, or 4). 2 HP Rack Storage/12FC with two FCArray Cards, HP disks, and using a HP D8602A HBA in each server. See Shared Storage below. Any NIC that is HP and Microsoft approved. See Client LAN below. HP D5013A/B with crossover cable. See Intra-cluster LAN below. Direct from power mains, power conditioner or uninterruptible power supply (UPS) using any power conditioner or UPS. Redundant power distribution units (PDU's) are strongly recommended. L.16.05 or later (For 700 MHz servers, use L.18.04.05 or later) 1

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7

1
HP NetServer LH4
with
HP Rack Storage/12FC & HP Rack Storage/12
Cluster Configuration Guide
7 September 2000
(see
Versions
at the end of this document)
Introduction
This document defines the supported HP NetServer LH4 configurations using the HP Rack Storage/12FC and
Microsoft Cluster Server and one or two HP Rack Storage/12’s.
These configurations minimize single points
of failure (SPOF) and provide extended availability.
The specific configuration certified and supported by both
Hewlett-Packard and Microsoft is defined, as are other guidelines to assist you in configuring your clustered
NetServers.
This guide is prescriptive; it describes the configurations supported by HP.
Any deviance to these
configurations can result in an inoperative cluster or an operating cluster with degraded performance, hidden
SPOFs, etc., and therefore will not be supported by HP.
What’s Defined in a Cluster
Cluster
SPUs
Local and Shared Storage
Intra-cluster and Client LANs
Shared Storage Cabling
Cluster
Type of SPUs
HP NetServer LH4
Each node must be the same model SPU, but may have different clock
speeds, main memory sizes, cache sizes, and number of CPUs (2, 3, or 4).
Number of nodes
2
Shared Storage
HP Rack Storage/12FC with two FCArray Cards, HP disks, and using a
HP D8602A HBA in each server.
See
Shared Storage
below.
LANs:
Client LAN
Any NIC that is HP and Microsoft approved.
See
Client LAN
below.
Intra-cluster
(Heartbeat) LAN
HP D5013A/B with crossover cable. See
Intra-cluster LAN
below.
Power source
Direct from power mains, power conditioner or uninterruptible power
supply (UPS) using any power conditioner or UPS. Redundant power
distribution units (PDU’s) are strongly recommended.
System software:
Navigator version
L.16.05 or later
(For 700 MHz servers, use L.18.04.05 or later)