HP StorageWorks Disk System 2100 / 2110 11 Power Connector FIGURE 6 AC Power Connector Location English AC Power Connector Electrical Requirements AC Site Requirements Overcurrent protection devices are required for each cabinet where the disk system is installed. They must be positioned between the power source and the disk system. These protective devices must not trip when exposed to an inrush current of 30 amps lasting 5 ms. Note These protection devices must meet all applicable electrical safety requirements and be approved for the intended purpose. I TABLE 3 AC Power Requirements Electrical Element Voltage Frequency Input Current Maximum Surge Current Requirements 100-240 VAC 50-60 Hz < 1 amp 30 amps peak

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42

11
HP
StorageWorks Disk System 2100 / 2110
English
Power Connector
FIGURE 6
AC Power Connector Location
Electrical Requirements
AC Site Requirements
Overcurrent protection devices are required for each cabinet where the disk system is
installed. They must be positioned between the power source and the disk system.
These protective devices must not trip when exposed to an inrush current of 30 amps
lasting 5 ms.
I
Note
These protection devices must meet all applicable electrical safety
requirements and be approved for the intended purpose.
TABLE 3
AC Power Requirements
Electrical Element
Requirements
Voltage
100-240 VAC
Frequency
50-60 Hz
Input Current
< 1 amp
Maximum Surge Current
30 amps peak
AC
Power
Connector