HP Surestore Disk Array 12h HP SureStore E Disk Array FC60 Service Manual (A56 - Page 116
Table 10, Measurement, Value, Number of, Components, Breaker, Rating, Breaker Type
![]() |
View all HP Surestore Disk Array 12h manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 116 highlights
Table 10 Disk Enclosure Electrical Requirements Measurement Value Voltage - Range - Frequency 220-240V 100 - 127V 50-60Hz Current - Typical Maximum Operating - 100 - 120 V - 200 - 240 V - Maximum In-rush 2.9 - 3.2A 2.6 - 3.2A 5.3 - 6.7A 20A * In-rush current occurs for 10 to 12 milliseconds HP recommends the use of magnetic-type circuit breakers, which are capable of handling large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately for the steady state currents. Table 11 Recommended European Circuit Breakers* Number of Breaker Components Rating Breaker Type 1 to 3 16 amps Type C or Type D per IEC 898 or Type K per IEC 947-2 Type D per IEC 898 4 16 amps or Type K per IEC 947-2 * Data assumes no other devices share the circuit breaker. Note Circuit breaker rating must be adequate for the total current drawn by all devices on all electrical paths that share a circuit breaker. 116 Site Requirements