HP rp7400 Site Preprepation - rp7400 - Page 17
Specify the System Requirements
View all HP rp7400 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 17 highlights
Table 3 Specify the System Requirements System Electrical Specifications Description Specification AC Input Voltage Rangea 200 to 240 VAC AC Input Line frequency 50 to 60 Hz AC Input Current 18 A (max load at 200 VAC)12 A (max load at 240 VAC) AC Inrush Current TBD AC Input Power 1250 VA maximum Power Supply Output Rating 1163 watts DC continuous Holdup without system reset 25ms at 50/60Hz (1 cycle, or 500ms) Battery Backup Time 15 minutes With optional external PowerTrust UPS. Without the optional UPS there is no battery backup. a. The power supply auto-ranges to the AC voltage and frequency. It does not have to be reconfigured to operate over its rated operating ranges. 17
17
Specify the System Requirements
System Electrical Specifications
Table 3
Description
Specification
AC Input Voltage Range
a
200 to 240 VAC
AC Input Line frequency
50 to 60 Hz
AC Input Current
18 A (max load at 200 VAC)12 A (max load at 240
VAC)
AC Inrush Current
TBD
AC Input Power
1250 VA maximum
Power Supply Output
Rating
1163 watts DC continuous
Holdup without system
reset
25ms at 50/60Hz (1 cycle, or 500ms)
Battery Backup Time
15 minutes
With optional external PowerTrust UPS. Without
the optional UPS there is no battery backup.
a. The power supply auto-ranges to the AC voltage and frequency. It does
not have to be reconfigured to operate over its rated operating ranges.