Honeywell 191108AJ Owner's Manual - Page 21
VoltageAtTimerTerminals
View all Honeywell 191108AJ manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
VoltageAtTimerTerminals AC Voltages at C-C Terminals 0 Vac. Up to 15 Vac. 15 to 30 Vac. Check - System power off. - Short in timer power supply wiring. - Limit switch contacts stuck open. - Transformer supplying power is burned out. - System transformer used to power the timer is inadequate. - Additional (separate) transformer used to power the timer has inadequate voltage. - Spring fingers on thermostat not making proper contact with subbase terminals. - Timer has failed. Action - Restore power. - Replace wiring. - Free or replace limit switch. - Replace transformer. - Use additional (separate) transformer. - Install transformer with proper secondary voltage. - Rebend spring fingers to a 45 degree angle to assure proper contact. - Replace thermostat. 21 69-0643-1