Honeywell AQ1000TP2 Owners Guide - Page 25
Vacancy Heating Setpoint, Vacancy Cooling Setpoint, Minimum Floor Limit, Maximum Floor Limit
View all Honeywell AQ1000TP2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Vacancy Heating Setpoint This parameter is the heating setpoint when the thermostat is in Vacancy mode (see page 4). Default setting 41 °F (5 °C) Range between the minimum and maximum setpoints Vacancy Cooling Setpoint This parameter is the cooling setpoint when the thermostat is in Vacancy mode (see page 4). Default setting 81 °F (27 °C) Range between the minimum and maximum setpoints Minimum Floor Limit This parameter is available only if the thermostat is configured in AF mode (see page 19). Heating is activated, regardless of setpoint, if the floor temperature is equal to this setting or below. Default setting 41 °F (5 °C) Range 41 °F (5 °C) to 100 °F (38 °C) Maximum Floor Limit This parameter is available only if the thermostat is configured in AF mode (see page 19). Heating is disabled, regardless of setpoint, if the floor temperature is equal to this setting or above. Default setting 100 °F (38 °C) Range 41 °F (5 °C) to 100 °F (38 °C) 22 69-2245EF