Honeywell DG115EZIAQ Owners Guide - Page 22
ventilation
UPC - 085267313025
View all Honeywell DG115EZIAQ manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 22 highlights
Advanced programming Setup functions 150 ASHRAE: CFM Setting 155 Maximum Vent 160 Vent Shut-offs 165 Dehumidification Via Fresh Air Ventilator Settings & Options (factory default in bold) 3=30 CFM; 4=40 CFM, up to 20=200 CFM 00; 30%-95%. (00 setting runs to ASHRAE 100%) 0-Auto vent regardless of outdoor conditions 1=Off at 75°F dew point or 99°F air temp 2=Low speed at 65°F dew point or 85°F air temp. Off at 75°F dew point or 99°F air temp Note: If option 1 or 2 is selected, then ASHRAE 62.2 Standard will not be met. 0=Do not use ventilation for dehum 1=Allow vent for dehum per outdoor conditions. With dehum installed, control to setpoint. Without dehum installed, control to the Hum setpoint +10% (max 60%). 69-2072-05 69-2072_C.indd 20 20 7131/2008 2:04:28 PM