Troubleshooting No. of Fault Steps to Fix Red Description To be Performed by Professional Light HVAC Technician Only Blinks 3 Failure to • Ensure inlet water is on. fill tank with • Check for leaks around the tank water. seal and solenoid valve. • Turn off water supply and replace in-line water filter. • Press/hold RESET button until the red Call Service light turns off. • If tank still fails to fill, press and hold the EMPTY button for 3 seconds (if unit fails to drain, unplug unit and make sure water in tank is cool). • Follow tank cleaning instructions in the Professional Installation Guide. Ensure you have a firm grip of the tank prior to releasing the tank, especially if water is present. • Clear any excess debris from the tank's bottom orifice to the solenoid valve. • Reassemble tank and plug unit back in. Press the RESET button. • If water still fails to flush into the tank, replace the solenoid valve. 4 Heating • Press and hold the EMPTY element button for 3 seconds. overheated. • Follow tank cleaning steps in the Professional Installation Guide. • Reassemble tank and press the RESET button. • If fault returns, replace with applicable unit. 5 Input voltage • Problem most likely due to insufficient. voltage variation from service provider, or faulty wiring in the home. If problem is due to TrueSTEAM service alone, the fault should correct itself when voltage levels return to normal. • Press and hold the RESET button until CALL SERVICE light shuts off. • Initiate a humidistat call for humidity and monitor for fault light to return. • If fault returns, check the line cord input voltage before and during humidistat call. Line voltage should not drop below 102Vrms to ensure TrueSTEAM operates properly. 6 Troubleshooting No. of Fault Steps to Fix Red Description To be Performed by Professional Light HVAC Technician Only Blinks 6 Water • Ensure drain hose is not kinked overflow sensed. or submerged in water at the drain. Check functionality of condensate pump if used. • Check for water coming out of drain/overflow line. If continuous water flow is present, follow the cleaning steps in the Professional Installation Guide (69-2036). • After cleaning, set humidistat on and monitor operation. • If fault returns, unplug TrueSTEAM. • Loosen cover screw and remove cover. • Disconnect water level sensor wiring and lift snap-hinge clamp to remove water sensor assembly. See image on page 5. • Clean probes using warm soapy water so that the metal is exposed. It is OK to use steel wool or brush. • Reassemble the sensor assembly in the unit, reattach and secure cover. • Plug unit in, and press RESET button. • If fault reappears, replace water sensor assembly and/or solenoid valve. 7 HVAC power • Turn humidistat off. not present. • At thermostat, validate that the FAN setting turns the blower on. If not, check the circuit breaker. If circuit is tripped, reset or replace fuse. • If fault persists, unplug TrueSTEAM and remove cover. • Validate proper TrueSTEAM wiring to R and C terminals, using installation guide (69-2036). • Ensure proper connection quality of the wires. • Inspect R and C wires at the HVAC equipment board, ensuring no breaks and good connection if wire nuts are used. • Hook AC volt meter across R and C to validate 20-30VAC is present. To measure, it may be necessary to close furnace interlock switch. • Secure TrueSTEAM cover and plug unit in. Press the RESET button. • If fault persists, recheck wiring or replace unit. Note: If using VisionPRO IAQ to control TrueSTEAM, it is not necessary to monitor HVAC power. DIP 4 may be turned on to disable monitor. 7 Troubleshooting No. of Fault Steps to Fix Red Description To be Performed by Professional Light HVAC Technician Only Blinks 8-11 12 13 14 The backup • Replace the TrueSTEAM unit. weld monitor input is active when the backup heater relay is off. Temperature • Ensure ventilation holes in the of the electronic circuit board is too high. cover are clear of obstruction, and that 1 foot of clearance is maintained around the cover's ventilation holes. • Ensure the TrueSTEAM is installed in a location with conditioned air 32°F (0°C) to 104°F (40°C). • Turn humidistat off and allow time for electronic board to cool. Unplugging unit and removing cover will facilitate this. • Turn humidistat on and press RESET button. • Confirm humidity call starts (HUMIDIFYING light turns on). • Allow unit to run and check for steam leaks around tank and ventilation holes. • If steam is present, replace TrueSTEAM. Tank failed to drain. • Water in tank may be hot (>140ºF [60ºC]) and can cause burns. • Press and hold the EMPTY button for 3 seconds. • If unit fails to drain, turn humidistat to OFF, or unplug the humidifier and wait for water in tank to cool. Ensure tank water is cool before proceeding. • Once cool, follow tank cleaning steps in the Professional Installation Guide (69-2036EFS). • Reassemble tank and press the RESET button. • If fault persists, replace the solenoid valve. Heater failed • Press and hold EMPTY button to boil water. for 3 seconds, and follow tank cleaning steps in the Professional Installation Guide. • Reassemble tank and press the RESET button. • Initiate humidistat call. • If fault returns, replace the unit. 8 Troubleshooting No. of Fault Steps to Fix Red Description To be Performed by Professional Light HVAC Technician Only Blinks 15 No Airflow. • Unplug TrueSTEAM and remove cover • Validate proper wiring to terminals R and C, using the diagrams in the installation guide (69-2036). • Ensure proper connection quality of the wires. • Inspect R and C wires at the HVAC equipment board, ensuring no breaks and good connection if wire nuts are used. • Hook AC volt meter across airflow switch normally-open (N.O.) terminal and R. • Set thermostat FAN to off and reduce system setpoint. • Validate 0 VAC reading on AC Volt Meter • Set thermostat FAN to on. • Once blower starts, validate 20- 30VAC reading on AC volt meter. • If voltage is not present, check wiring and switch functionality. Differential pressure switch may require a new install location (away from duct bends, etc), or it may need to be replaced. • If voltage is present, continue to troubleshoot to validate proper airflow monitoring. • Keep AC volt meter across airflow switch N.O. terminal and R from HVAC unit. • Turn humidistat off. • Ensure DIP 4 and 5 are in off (down) position. • Secure TrueSTEAM cover and plug in unit. Press the RESET button. • Set thermostat FAN to off and reduce system set point. • Set humidistat call and monitor device. (may take 15-20 minutes) • When sound of blower clears, validate within 2 minutes that the AC volt meter reads 20-30VAC. • If time for switch to change state takes longer than 2 minutes, try a new install location for the switch, where state change is faster. TrueSTEAM HM512, HM509, and HM506 Troubleshooting and parts replacement guide 9 69-2144-03

  • 1
  • 2

6
7
8
9
TrueSTEAM
HM512, HM509, and HM506
TROUBLESHOOTING AND
PARTS REPLACEMENT GUIDE
69-2144-03
TROUBLESHOOTING
No. of
Red
Light
Blinks
Fault
Description
Steps to Fix
To be Performed by Professional
HVAC Technician Only
8–11
The backup
weld monitor
input is
active when
the backup
heater relay
is off.
• Replace the TrueSTEAM unit.
12
Temperature
of the elec-
tronic circuit
board is too
high.
• Ensure ventilation holes in the
cover are clear of obstruction,
and that 1 foot of clearance is
maintained around the cover’s
ventilation holes.
• Ensure the TrueSTEAM is
installed in a location with
conditioned air 32°F (0°C) to
104°F (40°C).
• Turn humidistat off and allow
time for electronic board to cool.
Unplugging unit and removing
cover will facilitate this.
• Turn humidistat on and press
RESET button.
• Confirm humidity call starts
(HUMIDIFYING light turns on).
• Allow unit to run and check for
steam leaks around tank and
ventilation holes.
• If steam is present, replace
TrueSTEAM.
13
Tank failed
to drain.
• Water in tank may be hot (>140ºF
[60ºC]) and can cause burns.
• Press and hold the EMPTY
button for 3 seconds.
• If unit fails to drain, turn
humidistat to OFF, or unplug the
humidifier and wait for water in
tank to cool. Ensure tank water
is cool before proceeding.
• Once cool, follow tank cleaning
steps in the Professional
Installation Guide (69-2036EFS).
• Reassemble tank and press the
RESET button.
• If fault persists, replace the
solenoid valve.
14
Heater failed
to boil water.
• Press and hold EMPTY button
for 3 seconds, and follow
tank cleaning steps in the
Professional Installation Guide.
• Reassemble tank and press the
RESET button.
• Initiate humidistat call.
• If fault returns, replace the unit.
TROUBLESHOOTING
No. of
Red
Light
Blinks
Fault
Description
Steps to Fix
To be Performed by Professional
HVAC Technician Only
3
Failure to
fill tank with
water.
• Ensure inlet water is on.
• Check for leaks around the tank
seal and solenoid valve.
• Turn off water supply and
replace in-line water filter.
• Press/hold RESET button until
the red Call Service light turns
off.
• If tank still fails to fill, press and
hold the EMPTY button for 3
seconds (if unit fails to drain,
unplug unit and make sure water
in tank is cool).
• Follow tank cleaning instructions
in the Professional Installation
Guide. Ensure you have a firm
grip of the tank prior to releasing
the tank, especially if water is
present.
• Clear any excess debris from
the tank’s bottom orifice to the
solenoid valve.
• Reassemble tank and plug unit
back in. Press the RESET button.
• If water still fails to flush into the
tank, replace the solenoid valve.
4
Heating
element
overheated.
• Press and hold the EMPTY
button for 3 seconds.
• Follow tank cleaning steps in the
Professional Installation Guide.
• Reassemble tank and press the
RESET button.
• If fault returns, replace with
applicable unit.
5
Input voltage
insufficient.
• Problem most likely due to
voltage variation from service
provider, or faulty wiring in
the home. If problem is due to
TrueSTEAM service alone, the
fault should correct itself when
voltage levels return to normal.
• Press and hold the RESET button
until CALL SERVICE light shuts off.
• Initiate a humidistat call for
humidity and monitor for fault
light to return.
• If fault returns, check the line
cord input voltage before and
during humidistat call. Line
voltage should not drop below
102Vrms to ensure TrueSTEAM
operates properly.
TROUBLESHOOTING
No. of
Red
Light
Blinks
Fault
Description
Steps to Fix
To be Performed by Professional
HVAC Technician Only
15
No Airflow.
• Unplug TrueSTEAM and remove
cover
• Validate proper wiring to
terminals R and C, using the
diagrams in the installation guide
(69-2036).
• Ensure proper connection quality
of the wires.
• Inspect R and C wires at the
HVAC equipment board, ensuring
no breaks and good connection
if wire nuts are used.
• Hook AC volt meter across
airflow switch normally-open
(N.O.) terminal and R.
• Set thermostat FAN to off and
reduce system setpoint.
• Validate 0 VAC reading on AC
Volt Meter
• Set thermostat FAN to on.
• Once blower starts, validate 20-
30VAC reading on AC volt meter.
• If voltage is not present, check
wiring and switch functionality.
Differential pressure switch may
require a new install location
(away from duct bends, etc), or it
may need to be replaced.
• If voltage is present, continue to
troubleshoot to validate proper
airflow monitoring.
• Keep AC volt meter across
airflow switch N.O. terminal and
R from HVAC unit.
• Turn humidistat off.
• Ensure DIP 4 and 5 are in off
(down) position.
• Secure TrueSTEAM cover and
plug in unit. Press the RESET
button.
• Set thermostat FAN to off and
reduce system set point.
• Set humidistat call and monitor
device. (may take 15-20 minutes)
• When sound of blower clears,
validate within 2 minutes that the
AC volt meter reads 20-30VAC.
• If time for switch to change state
takes longer than 2 minutes,
try a new install location for the
switch, where state change is
faster.
TROUBLESHOOTING
No. of
Red
Light
Blinks
Fault
Description
Steps to Fix
To be Performed by Professional
HVAC Technician Only
6
Water
overflow
sensed.
• Ensure drain hose is not kinked
or submerged in water at the
drain. Check functionality of
condensate pump if used.
• Check for water coming out of
drain/overflow line. If continuous
water flow is present, follow
the cleaning steps in the
Professional Installation Guide
(69-2036).
• After cleaning, set humidistat on
and monitor operation.
• If fault returns, unplug TrueSTEAM.
• Loosen cover screw and remove
cover.
• Disconnect water level sensor
wiring and lift snap-hinge
clamp to remove water sensor
assembly. See image on page 5.
• Clean probes using warm
soapy water so that the metal
is exposed. It is OK to use steel
wool or brush.
• Reassemble the sensor
assembly in the unit, reattach
and secure cover.
• Plug unit in, and press RESET
button.
• If fault reappears, replace water
sensor assembly and/or solenoid
valve.
7
HVAC power
not present.
• Turn humidistat off.
• At thermostat, validate that the
FAN setting turns the blower on.
If not, check the circuit breaker.
If circuit is tripped, reset or
replace fuse.
• If fault persists, unplug
TrueSTEAM and remove cover.
• Validate proper TrueSTEAM
wiring to R and C terminals, using
installation guide (69-2036).
• Ensure proper connection quality
of the wires.
• Inspect R and C wires at the
HVAC equipment board, ensuring
no breaks and good connection
if wire nuts are used.
• Hook AC volt meter across R and
C to validate 20-30VAC is present.
To measure, it may be necessary
to close furnace interlock switch.
• Secure TrueSTEAM cover and plug
unit in. Press the RESET button.
• If fault persists, recheck wiring or
replace unit.
Note:
If using VisionPRO IAQ to
control TrueSTEAM, it is not
necessary to monitor HVAC
power. DIP 4 may be turned on
to disable monitor.