Honeywell HPF24S6 Installation Manual - Page 11

Auxiliary Special Application Power Output - TB4 Terminals 9 + & 10

Page 11 highlights

Specifications System Overview Control Input Circuits - TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-) • Trigger Input Voltage: 9 to 32 VDC • Input Current Draw in Alarm Polarity: - 16 to 32 volts, 16.0 mA maximum per input - 9 to 16 volts, 6.0 mA maximum per input NAC/Output Circuits - TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and 7 (+) & 8 (-) alarm polarity • Supervised and power-limited (Class 2) • Voltage Rating: 24 VDC filtered • Current: - Maximum for any one circuit - 3.0 amps special application, 300mA regulated - Maximum total continuous current for all output: HPF24S6 - 4.0 amps HPF24S8 - 6.0 amps - Maximum total short term current (one hour maximum) for all outputs: HPF24S6 - 6.0 amps HPF24S8 - 8.0 amps • Output Circuit Types: - Four Style Y NACs (require 4.7 KEnd-of-Line Resistors) or Style Z NACs using the optional ZNAC-4 Class A converter module OR - Four resettable or nonresettable 24 VDC power outputs • Refer to the HPP Device Compatibility Document #54399 for listed compatible devices. • For wiring requirements, refer to "Wire Requirements" on page 43. Trouble Relay Contact Rating - TB5 • Fail-safe Form-C relay (normally energized, transfers with loss of power) • 5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC Secondary Power (battery) Charging Circuit - JP4 • Supervised, nonpower-limited • Supports lead acid type batteries only • Float Charge Voltage: 27.6 VDC • Maximum Charge Current: 1.5 A • Battery fuse (F1) 15A, 32V (Canadian version is nonreplaceable 12A, 32V) • Maximum Battery Capacity: 18.0 AH • Minimum Battery Capacity: 7.0 AH • Power supply draws maximum standby current of 65 mA from batteries Auxiliary Special Application Power Output - TB4 Terminals 9 (+) & 10 (-) • Special application power • Power-limited (Class 2), nonsupervised • Voltage Rating: 24 VDC • Current: - 170 mA maximum with internal 7.0 Amp Hour batteries - 500 mA maximum with external 18.0 Amp Hour batteries HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
11
Specifications
System Overview
Control Input Circuits
- TB4, Terminals 3 (+) & 4 (-)
and 7 (+) & 8 (-)
Trigger Input Voltage: 9 to 32 VDC
Input Current Draw in Alarm Polarity:
16 to 32 volts, 16.0 mA maximum per input
9 to 16 volts, 6.0 mA maximum per input
NAC/Output Circuits - TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and
7 (+) & 8 (-) alarm polarity
Supervised and power-limited (Class 2)
Voltage Rating: 24 VDC filtered
Current:
Maximum for any one circuit - 3.0 amps special application, 300mA regulated
Maximum total continuous
current for all output:
HPF24S6 - 4.0 amps
HPF24S8 - 6.0 amps
Maximum total short term
current (one hour maximum) for all outputs:
HPF24S6 - 6.0 amps
HPF24S8 - 8.0 amps
Output Circuit Types:
Four Style Y NACs (require 4.7 K
End-of-Line Resistors) or
Style Z NACs using the optional ZNAC-4 Class A converter module
OR
Four resettable or nonresettable 24 VDC power outputs
Refer to the
HPP Device Compatibility Document #54399
for listed compatible devices.
For wiring requirements, refer to “Wire Requirements” on page 43.
Trouble Relay Contact Rating - TB5
Fail-safe Form-C relay (normally energized, transfers with loss of power)
5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC
Secondary Power (battery) Charging Circuit
- JP4
Supervised, nonpower-limited
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Charge Current: 1.5 A
Battery fuse (F1) 15A, 32V (Canadian version is
nonreplaceable
12A, 32V)
Maximum Battery Capacity: 18.0 AH
Minimum Battery Capacity: 7.0 AH
Power supply draws maximum standby current of 65 mA from batteries
Auxiliary Special Application Power Output - TB4 Terminals 9 (+) & 10 (-)
Special application power
Power-limited (Class 2), nonsupervised
Voltage Rating: 24 VDC
Current:
170 mA maximum with internal 7.0 Amp Hour batteries
500 mA maximum with external 18.0 Amp Hour batteries