Honeywell HPF24S6 Installation Manual - Page 31

Controlling Three NACs and One Door Holder With One Input

Page 31 highlights

Controlling Three NACs and One Door Holder With One Input Applications The control module is shown to demonstrate the use of a remotely mounted device associated with an addressable fire alarm control panel. The module could be replaced with any circuit capable of polarity reversal, such as an FACP Notification Appliance Circuit. Note: All NACs are supervised and power-limited (Class 2) ELR not required for Style Z (Class A) NAC Door Holder Horn/Strobes Alarm Polarity Shown Use listed ELR (4.7K) to terminate Style Y (Class B) NAC Door Holder Horn/Strobes Alarm Polarity Shown Internal Trouble Contact HPF24S Style Z (Class A) ZNAC-4 Option Module SLC End-of-Line Resistor supplied with Control Module Style Y (Class B) Door Holder Circuit 4 Output/NAC 3 Output/NAC 2 Output/NAC 1 SW1 Switch Settings 1 & 2 = sync (any setting but OFF/OFF) 3 = OFF (master) 4 = OFF (no AC Fail reporting delay) 5 6 = = OFF OFF (general alarm) 7 = OFF (charger enabled) 8 = ON (circuit 4 door holder) 24fsapp6tpH.wmf Control Module* *If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules. Figure 5.2 Controlling Three NACs and One Door Holder With One Input The following notes apply to Figure 5.2 on page 31. 1. The Output 4 door holder circuit will deactivate 10 seconds after Control Input #1 is activated or AC power is lost. 2. When the HPF24S power supply is in an inactive state (control module not active), a trouble on the power supply will result in an open circuit condition on the control module output circuit (monitored by an End-of-Line Resistor across Terminals 5 & 6). As an alternative, the trouble contacts at TB5 of the power supply can also be used for independent trouble monitoring. 3. Do not loop wires under screw terminals. Break wires to maintain proper supervision. 4. An End-of-Line Resistor must be installed between terminals 5 & 6 for control module wiring supervision (the ELR value is dependent on the module employed). 5. For a list of compatible devices, refer to the HPP Device Compatibility Document #54399. HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014 31

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
31
Controlling Three NACs and One Door Holder With One Input
Applications
The control module is shown to demonstrate the use of a remotely mounted device associated with
an addressable fire alarm control panel. The module could be replaced with any circuit capable of
polarity reversal, such as an FACP Notification Appliance Circuit.
The following notes apply to Figure 5.2 on page 31.
1.
The Output 4 door holder circuit will deactivate 10 seconds after Control Input #1 is activated
or AC power is lost.
2.
When the HPF24S power supply is in an inactive state (control module not active), a trouble
on the power supply will result in an open circuit condition on the control module output
circuit (monitored by an End-of-Line Resistor across Terminals 5 & 6).
As an alternative, the
trouble contacts at TB5 of the power supply can also be used for independent trouble
monitoring.
3.
Do not loop wires under screw terminals.
Break wires to maintain proper supervision.
4.
An End-of-Line Resistor must be installed between terminals 5 & 6 for control module wiring
supervision (the ELR value is dependent on the module employed).
5.
For a list of compatible devices, refer to the
HPP Device Compatibility Document #54399
.
Figure 5.2
Controlling Three NACs and One Door Holder With One Input
Style Z (Class A)
Style Y (Class B)
Door Holder Circuit 4
Output/NAC 3
Output/NAC 2
Output/NAC 1
Use listed ELR
(4.7K
) to
terminate Style Y
(Class B) NAC
ELR not required for
Style Z (Class A) NAC
Door Holder
Door Holder
Note: All NACs are supervised and power-limited (Class 2)
ZNAC-4
Option Module
SW1 Switch Settings
1 & 2 = sync (any setting but OFF/OFF)
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = ON (circuit 4 door holder)
Internal Trouble Contact
(general alarm)
Control Module*
SLC
End-of-Line Resistor
supplied with Control
Module
HPF24S
Horn/Strobes
Alarm Polarity
Shown
Horn/Strobes
Alarm Polarity
Shown
24fsapp6tpH.wmf
*If the SLC device does not match the one in this figure, refer to the SLC man-
ual wiring conversion charts for legacy and newer versions of the modules.