Honeywell RTH2520B1008A Owner's Manual - Page 1

Honeywell RTH2520B1008A - International 7 Day Program Thermostat Manual

Page 1 highlights

RTH2520 Programmable Thermostat Installation and User Guide 1. Introduction The RTH2520 programmable thermostat can be used to control: • a gas, fuel oil or electric furnace -2 or 3 wires • a central air conditioner - 2 or 3 wires • a hot water system with or without pump - 2 wires • a millivolt system - 2 wires • a central heating and cooling system - 4 or 5 wires Note: This thermostat is not compatible with heat pumps or multistage systems.  Identify and label each wire (with the corresponding letter on the wire terminal) and remove them from the terminals.  If necessary, strip the end of each wire (maximum of 1/4 inch).  Wrap the wires around a pencil to prevent them from falling into the wall.  If the hole in the wall is too big, insulate it using a non-flammable material in order to avoid air draughts behind the thermostat. 2.2 Installing the New Baseplate For a new installation, choose a location approximately 5 feet (1.5 m) above the floor and on an inside wall. Avoid draughty areas (top of staircase, air outlet, etc.), dead air spots (behind doors), direct sunlight or areas near concealed pipes or chimneys. Display Adjustment buttons Backlight button  Remove the thermostat faceplate.  Loosen the locking screw in order to separate the thermostat from its baseplate (the screw cannot be completely removed). System operating mode selector Fan operating mode selector Programming buttons Features • System operating mode selection: heat, cool or off • Fan operating mode selection: automatic or on (continuous) • Programmable heating and cooling cycle lengths: 10, 12, 15, 20 or 30 minutes • Temperature display in °F or °C • Backlit display • Battery replacement indicator • 7-day programming including: - Preprogrammed energy-saving schedule - Early Start - Temporary bypass - Time display (12 h or 24 h) • Filter replacement indicator • Automatic daylight savings changeover • Interchangeable faceplates (titanium, charcoal & taupe) 2. Installation 2.1 Removing the Old Thermostat IN ORDER TO AVOID ANY RISK OF ELECTRIC SHOCK, CUT POWER TO THE HEATING/COOLING SYSTEM.  Remove the old thermostat to access the wires. Warning: If the old thermostat was mounted onto an electrical box, it was probably powered by 120/240 volts. In this case, this thermostat cannot be used. RTH2520  Gently tilt the thermostat upwards.  Mark and bore the appropriate mounting holes (using a 3/16" drill bit) or use the existing holes. Insert the plastic anchors.  Pass the wires through the opening of the baseplate and fix the baseplate to the wall using the screws provided. 2.3 Connecting the Thermostat Refer to the following table for matching the wire labels with the thermostat terminals. RTH2520 terminals Rh Rc W Y G Description Heating power supply Cooling power supply Heating signal Cooling signal Fan Wire labels Rh, R, 4, V Rc, R W, W1, H Y, Y1, M G, F Note: Do not connect wires identified as C, X or B. Wrap the bare end of these wires with electrical tape. Important: The red jumper wire between Rh and Rc terminals must be removed in a 5-wire installation. 69-1867ES-05 69-1867ES-05 03-11 1/8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

RTH2520
69-1867ES—05
03-11
1/8
The RTH2520 programmable thermostat can be used to control:
a gas, fuel oil or electric furnace -2 or 3 wires
a central air conditioner - 2 or 3 wires
a hot water system with or without pump - 2 wires
a millivolt system - 2 wires
a central heating and cooling system - 4 or 5 wires
Note
: This thermostat is not compatible with heat pumps or multi-
stage systems.
Features
System operating mode selection: heat, cool or off
Fan operating mode selection: automatic or on (continuous)
Programmable heating and cooling cycle lengths: 10, 12, 15, 20
or 30 minutes
Temperature display in °F or °C
Backlit display
Battery replacement indicator
7-day programming including:
- Preprogrammed energy-saving schedule
- Early Start
- Temporary bypass
- Time display (12 h or 24 h)
Filter replacement indicator
Automatic daylight savings changeover
Interchangeable faceplates (titanium, charcoal & taupe)
2.1
Removing the Old Thermostat
IN ORDER TO AVOID ANY RISK OF ELECTRIC SHOCK, CUT
POWER TO THE HEATING/COOLING SYSTEM.
Remove the old thermostat to access the wires.
Warning
: If the old thermostat was mounted onto an electrical box,
it was probably powered by 120/240 volts. In this case, this thermo-
stat cannot be used.
Identify and label each wire (with the corresponding letter on
the wire terminal) and remove them from the terminals.
If necessary, strip the end of each wire (maximum of 1/4 inch).
Wrap the wires around a pencil to prevent
them from falling into the wall.
If the hole in the wall is too big, insulate it
using a non-flammable material in order to
avoid air draughts behind the thermostat.
2.2
Installing the New Baseplate
For a new installation, choose a location approximately 5 feet
(1.5 m) above the floor and on an inside wall. Avoid draughty
areas (top of staircase, air outlet, etc.), dead air spots (behind
doors), direct sunlight or areas near concealed pipes or chim-
neys.
Remove the thermostat faceplate.
Loosen the locking screw in order to separate the thermostat
from its baseplate (the screw cannot be completely removed).
Gently tilt the thermostat upwards.
Mark and bore the appropriate mounting holes (using a 3/16”
drill bit) or use the existing holes. Insert the plastic anchors.
Pass the wires through the opening of the baseplate and fix the
baseplate to the wall using the screws provided.
2.3
Connecting the Thermostat
Refer to the following table for matching the wire labels with the
thermostat terminals.
Note
: Do not connect wires identified as C, X or B. Wrap the bare
end of these wires with electrical tape.
Important
: The red jumper wire between Rh and Rc terminals must
be removed in a 5-wire installation.
1. Introduction
2. Installation
RTH2520
Programmable Thermostat
Installation and User Guide
Adjustment
buttons
Display
System operating
mode selector
Fan operating
mode selector
Backlight
button
Programming
buttons
RTH2520 terminals
Description
Wire labels
Rh
Heating power supply
Rh, R, 4, V
Rc
Cooling power supply
Rc, R
W
Heating signal
W, W1, H
Y
Cooling signal
Y, Y1, M
G
Fan
G, F
69-1867ES-05