TB6980/TB7980 1. Introduction Installation and User Guide ZonePRO Thermostats The TB6980/TB7980 digital thermostats provide proportional plus integral individual space temperature control in zoned commercial HVAC systems such as hydronic and pressure dependent VAV with or without reheat. There are four different models: • TB7980A (single output, modulating) • TB6980A (single output, floating) • TB7980B (multiple output modulating) • TB6980B (multiple output, floating) Depending on the models, the thermostat can have up to three outputs for the following applications:  Floating or Modulating damper/valve actuator control  Damper/valve actuator control with duct reheat and auxiliary heat (B models only)  Hydronic systems (room control, perimeter heating and cool- ing) Accessories  R841 family of electromechanical relays  T7770A3002 remote room sensor  50014156-002 remote room sensor  32004800-001 bare thermistor  50014157-001 duct temperature sensor 2. Installation Configuration and status display Cooling mode Temperature adjustment button Override button Heating mode Temperature display Output power display 2.1 Mounting Instructions 1. Remove the thermostat from its base by unscrewing the captive screw and tilting the bottom of the thermostat up. The screw cannot be completely removed. 2. Pass the wires through the center hole of the base and secure the base to the wall or onto an electrical box. 3. Wire the thermostat. See section 2.2 for terminal designations and section 3 for typical wiring diagrams. 4. Reinstall the thermostat onto its base and secure with the captive screw. 2.2 Terminal Designations The designations of the terminals vary according to the particular model of thermostat. Refer to the following table for the description of each terminal. TERMINAL DESCRIPTION 1 24 VAC 2 COM Power supply 3 AN1 4 COM TB7980 models Output 1 3 OPEN 4 CLOSED TB6980 models 5 6 T2/AN2 T2/COM Output 2 (TB6980B and TB7980B models) 7 T3 8 T3 Output 3 (TB6980B and TB7980B models) 9 COM External sensor input. (For applications requiring 10 SENSOR an external sensor, see section 4.2.) 9 COM Mode Changeover input (N.O. contact). See sec- 11 C-Over tion 5.5.2. 9 COM 12 NSB Night Setback activation input (N.O. contact). See section 5.6. Note: To configure the terminals, see section 4. TB6980/TB7980 1/6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6

TB6980/TB7980
1/6
1. Introduction
The TB6980/TB7980 digital thermostats provide proportional plus
integral individual space temperature control in zoned commercial
HVAC systems such as hydronic and pressure dependent VAV with
or without reheat. There are four different models:
Depending on the models, the thermostat can have up to three out-
puts for the following applications:
Floating or Modulating damper/valve actuator control
Damper/valve actuator control with duct reheat and auxiliary
heat (B models only)
Hydronic systems (room control, perimeter heating and cool-
ing)
Accessories
R841 family of electromechanical relays
T7770A3002 remote room sensor
50014156-002 remote room sensor
32004800-001 bare thermistor
50014157-001 duct temperature sensor
2. Installation
2.1
Mounting Instructions
1.
Remove the thermostat from its base by unscrewing the cap-
tive screw and tilting the bottom of the thermostat up. The
screw cannot be completely removed.
2.
Pass the wires through the center hole of the base and secure
the base to the wall or onto an electrical box.
3.
Wire the thermostat. See section 2.2 for terminal designations
and section 3 for typical wiring diagrams.
4.
Reinstall the thermostat onto its base and secure with the cap-
tive screw.
2.2
Terminal Designations
The designations of the terminals vary according to the particular
model of thermostat. Refer to the following table for the description
of each terminal.
TB7980A (single output, modulating)
TB6980A (single output, floating)
TB7980B (multiple output modulating)
TB6980B (multiple output, floating)
Configuration and status display
Heating mode
Temperature display
Output power display
Temperature
adjustment
button
Cooling mode
Override button
TERMINAL
DESCRIPTION
1
2
24 VAC
COM
Power supply
3
4
AN1
COM
Output 1
TB7980 models
3
4
OPEN
CLOSED
TB6980 models
5
6
T2/AN2
T2/COM
Output 2 (TB6980B and TB7980B models)
7
8
T3
T3
Output 3 (TB6980B and TB7980B models)
9
10
COM
SENSOR
External sensor input. (For applications requiring
an external sensor, see section 4.2.)
9
11
COM
C-Over
Mode Changeover input (N.O. contact). See sec-
tion 5.5.2.
9
12
COM
NSB
Night Setback activation input (N.O. contact).
See section 5.6.
Note
: To configure the terminals, see section 4.
TB6980/TB7980
Installation and User Guide
ZonePRO Thermostats