Jenn-Air JGCP548HL Installation Instructions - Page 13

Gas Conversions

Page 13 highlights

GAS CONVERSIONS IMPORTANT: Gas conversions from Natural gas to Propane gas must be done by a qualified installer. WARNING Explosion Hazard Use a new CSA International approved gas supply line. Install a shut-off valve. To Convert Gas Pressure Regulator from Natural Gas to Propane 1. Remove the gas pressure regulator cap by using a large flat-blade screwdriver, turning the regulator cap counterclockwise. When the cap is removed, do not lose the metal seal. NOTE: Do not remove the spring beneath the cap. 2. Remove spring retainer from the cap by turning the spring retainer counterclockwise. Locate the "LP" and "NAT" position on the spring retainer. Turn over the spring retainer so the "LP" arrow is pointing toward the cap. A Securely tighten all gas connections. If connected to propane, have a qualified person make sure gas pressure does not exceed 14" (36 cm) water column. B Examples of a qualified person include: licensed heating personnel, authorized gas company personnel, and authorized service personnel. Failure to do so can result in death, explosion, or fire. C LP NAT D NAT LP NAT LP E LP NAT Propane Gas Conversion 1. Turn the manual shut-off valve to the closed position. B A C A. To cooktop B. Shut-off valve (closed position) C. Gas supply line 2. Unplug cooktop or disconnect power. A. Regulator cap B. Metal seal C. Gas pressure regulator D. Spring retainer in NAT position E. Spring retainer in LP position 3. Tighten the gas pressure regulator cap by using a large flat blade screwdriver, turning the regulator cap clockwise. 4. Test the gas pressure regulator and gas supply line. The regulator must be checked at a minimum 1" (2.5 cm) water column above the set pressure. The inlet pressure to the regulator should be as follows for operation and checking the regulator setting: Propane Gas: Minimum pressure: 10" (25.4 cm) WCP Maximum pressure: 14" (35.6 cm) WCP Gas Supply Pressure Testing Gas supply pressure for testing regulator must be at least 1" (2.5 cm) water column pressure above the manifold pressure shown on the model/serial/rating plate. Line pressure testing above 1/2 psi (3.5 kPa) gauge (14" [35.6 cm] WCP) The cooktop and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). Line pressure testing at 1/2 psi (3.5 kPa) gauge (14" [35.6 cm] WCP) or lower The cooktop must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa). 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

13
GAS CONVERSIONS
IMPORTANT:
Gas conversions from Natural gas to Propane gas
must be done by a qualified installer.
Propane Gas Conversion
1.
Turn the manual shut-off valve to the closed position.
2.
Unplug cooktop or disconnect power.
To Convert Gas Pressure Regulator from Natural Gas
to Propane
1.
Remove the gas pressure regulator cap by using a
large flat-blade screwdriver, turning the regulator cap
counterclockwise. When the cap is removed, do not lose the
metal seal.
NOTE:
Do not remove the spring beneath the cap.
2.
Remove spring retainer from the cap by turning the spring
retainer counterclockwise. Locate the “LP” and “NAT”
position on the spring retainer. Turn over the spring retainer so
the “LP” arrow is pointing toward the cap.
3.
Tighten the gas pressure regulator cap by using a large flat
blade screwdriver, turning the regulator cap clockwise.
4.
Test the gas pressure regulator and gas supply line.
The regulator must be checked at a minimum 1" (2.5 cm)
water column above the set pressure. The inlet pressure
to the regulator should be as follows for operation and
checking the regulator setting:
Propane Gas:
Minimum pressure: 10" (25.4 cm) WCP
Maximum pressure: 14" (35.6 cm) WCP
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least 1"
(2.5 cm) water column pressure above the manifold pressure
shown on the model/serial/rating plate.
Line pressure testing above 1/2 psi (3.5 kPa) gauge (14"
[35.6 cm] WCP)
The cooktop and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
Line pressure testing at 1/2 psi (3.5 kPa) gauge (14"
[35.6 cm] WCP) or lower
The cooktop must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to propane, have a qualified person make
sure gas pressure does not exceed 14" (36 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
A
B
C
A. To cooktop
B. Shut-off valve (closed position)
C. Gas supply line
LP
NAT
LP
NAT
LP
NAT
LP
NAT
A
B
C
D
E
A. Regulator cap
B. Metal seal
C. Gas pressure regulator
D. Spring retainer in NAT
position
E. Spring retainer in LP
position