Kenmore 33125 Owners Manual - Page 11
theinsulation - weather
View all Kenmore 33125 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 11 highlights
• DoobtainewwarninagndinstructiolanbelfsromSearfsor placemeonnttheblankedtirectloyvertheexistinlgabels. • Doinspectht einsulatiobnlankefrtequenttloymakecertain it doesnotsagt,hereboybstructincogmbustioanirflow. Combustion Air and Ventilation for Appliances Located in Unconfined Spaces UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space. In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confined Spaces. Combustion Air and Ventilation for Appliances Located in Confined Spaces CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the aggregate input rating of all appliances installed in that space. A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 9 on page 10 and Figure 10 below) The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,O00 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom of the enclosures. The confined space shall be provided with two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. CHIMNEY OR GAS VENT VENTILATION LOUVERS OUTLET MR 'WATERHEATER FURNACE INLETAIR DUCT ALT. INLET AiR VENTILATION LOUVERS FIGURE II. When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,0go Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 11. When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 12. CHIMNEY OR GAS VENT _.,_'(EAOH VENTiLATiON LOUVERS END OF ATT'C) AIR OUTLET _ WATER HEATER IIl ll LfJL ilq--I-NLE'TNAIRoDUsCT,'cR,oo.. ABOVE FLOOR) ___OP NT ENINGS FIGURE 10, B. ALL AIR FROM OUTDOORS: (See Figures 9, 11,12,13 and 13A) FIGURE 12. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour (11 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 13. When ducts are used, they shall be of the same crosssectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches (76.2 ram). See Figure 13. 11