Kenmore 33125 Owners Manual - Page 11

theinsulation - weather

Page 11 highlights

• DoobtainewwarninagndinstructiolanbelfsromSearfsor placemeonnttheblankedtirectloyvertheexistinlgabels. • Doinspectht einsulatiobnlankefrtequenttloymakecertain it doesnotsagt,hereboybstructincogmbustioanirflow. Combustion Air and Ventilation for Appliances Located in Unconfined Spaces UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space. In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confined Spaces. Combustion Air and Ventilation for Appliances Located in Confined Spaces CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the aggregate input rating of all appliances installed in that space. A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 9 on page 10 and Figure 10 below) The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,O00 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom of the enclosures. The confined space shall be provided with two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. CHIMNEY OR GAS VENT VENTILATION LOUVERS OUTLET MR 'WATERHEATER FURNACE INLETAIR DUCT ALT. INLET AiR VENTILATION LOUVERS FIGURE II. When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,0go Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 11. When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 12. CHIMNEY OR GAS VENT _.,_'(EAOH VENTiLATiON LOUVERS END OF ATT'C) AIR OUTLET _ WATER HEATER IIl ll LfJL ilq--I-NLE'TNAIRoDUsCT,'cR,oo.. ABOVE FLOOR) ___OP NT ENINGS FIGURE 10, B. ALL AIR FROM OUTDOORS: (See Figures 9, 11,12,13 and 13A) FIGURE 12. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour (11 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 13. When ducts are used, they shall be of the same crosssectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches (76.2 ram). See Figure 13. 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

• Doobtainewwarning
and
instruction
labels
fromSears
for
placement
ontheblanket
directly
over
theexisting
labels.
• Doinspect
theinsulation
blanket
frequently
tomakecertain
itdoesnotsag,
thereby
obstructing
combustion
airflow.
Combustion
Air
and
Ventilation
for
Appliances
Located
in Unconfined
Spaces
UNCONFINED
SPACE
is space
whose
volume
is not
less than
50
cubic
feet
per
1,000
Btu
per
hour
(4.8
m 3 per
kW)
of
the
aggregate
input
rating
of all appliances
installed
in that
space.
Rooms
communicating
directly
with
the
space
in
which
the
appliances
are
installed,
through
openings
not
furnished
with
doors,
are
considered
a part
of the
unconfined
space.
In unconfined
spaces
in buildings,
infiltration
may
be
adequate
to
provide
air
for
combustion,
ventilation
and
dilution
of
flue
gases.
However,
in buildings
of tight
construction
(for
example,
weather
stripping,
heavily
insulated,
caulked,
vapor
barrier,
etc.),
additional
air
may
need
to be provided
using
the
methods
described
in
Combustion
Air
and
Ventilation
for
Appliances
Located
in Confined
Spaces.
Combustion
Air
and
Ventilation
for
Appliances
Located
in Confined
Spaces
CONFINED
SPACE
is
a
space
whose
volume
is
less
than
50
cubic
feet
per
1,000
Btu
per
hour
(4.8
m 3 per
kW)
of the
aggregate
input
rating
of all appliances
installed
in that
space.
A.
ALL
AIR
FROM
INSIDE
BUILDINGS:
(See
Figure
9 on page
10 and
Figure
10 below)
The
confined
space
shall
be
provided
with
two
permanent
openings
communicating
directly
with
an
additional
room(s)
of
sufficient
volume
so
that
the
combined
volume
of
all
spaces
meets
the
criteria
for an
unconfined
space.
The
total
input
of all
gas
utilization
equipment
installed
in the
combined
space
shall
be considered
in making
this
determination.
Each
opening
shall
have
a minimum
free area
of one
square
inch
per
1,O00 Btu per
hour
(22
cm2/kW)
of
the
total
input
rating
of all
gas
utilization
equipment
in the
confined
space,
but
not
less
than
100
square
inches
(645 cm2).
One
opening
shall commence
within
12 inches
(30
cm)
of the
top
and
one
commencing
within
12 inches
(30
cm)
of the
bottom
of the
enclosures.
NT
___OP
ENINGS
FIGURE 10,
B. ALL AIR FROM OUTDOORS: (See Figures 9, 11,12,13 and 13A)
The
confined
space
shall
be
provided
with
two
permanent
openings,
one
commencing
within
12 inches
(30 cm)
of the
top
and
one
commencing
within
12 inches
(30 cm)
from
the
bottom
of the
enclosure.
The
openings
shall
communicate
directly,
or
by ducts,
with
the
outdoors
or spaces
(crawl
or attic)
that
freely
communicate
with
the
outdoors.
CHIMNEY
OR
GAS VENT
VENTILATION
LOUVERS
OUTLET
MR
'WATERHEATER
FURNACE
INLETAIR
DUCT
ALT.
INLET
AiR
VENTILATION
LOUVERS
FIGURE
II.
When
directly
communicating
with the outdoors,
each opening
shall
have
a minimum
free area
of 1 square
inch
per 4,0go
Btu
per hour
(5.5 cm2/kW)
of total
input
rating
of all equipment
in
the
enclosure.
See
Figure
11.
When
communicating
with
the
outdoors
through
vertical
ducts,
each
opening
shall
have
a
minimum
free
area
of
1
square
inch
per
4,000
BTU
per
hour
(5.5
cm2/kW)
of
total
input
rating
of
all
equipment
in the
enclosure.
See
Figure
12.
CHIMNEY
OR
GAS VENT
VENTiLATiON
LOUVERS
_.,_'(EAOH
END
OF
ATT'C)
AIR
OUTLET
_
WATER
HEATER
INLET
AIR
DUCT
IIl ll LfJL ilq--- 'Nos,'cR,oo..
ABOVE
FLOOR)
FIGURE 12.
When
communicating
with
the
outdoors
through
horizontal
ducts,
each
opening
shall
have
a
minimum
free
area
of
1
square
inch
per
2,000
BTU
per
hour
(11
cm2/kW)
of
total
input
rating
of
all
equipment
in the
enclosure.
See
Figure
13.
When
ducts
are
used,
they
shall
be
of
the
same
cross-
sectional
area
as
the
free
area
of
the
openings
to
which
they
connect.
The
minimum
short
side
dimension
of
rectangular
air
ducts
shall
not
be
less
than
3
inches
(76.2
ram).
See
Figure
13.
11