Kenmore 33204 Owners Manual - Page 19

Breathing, Hazard, Carbon, Monoxide

Page 19 highlights

Breathing Hazard - Carbon Monoxide Gas • Install vent system in accordance with codes. • Do not operate water heater if flood damaged • High altitude orifice must be installed for operation above7,700 feet (2,347 m). • Do not operate if soot buildup. • Do not obstruct water heater air intake with insulating jackeL • Do not place chemical vapor emitting products near water heater. • Gas and carbon monoxide detectors are available. • Never operate the heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation, fire, explosion, or asphyxiation. • Make sure the flue baffle and flue restrictor ring are properly aligned and inserted on top of the flue. This can be checked through the dilution air inlet of the blower assembly, For viewing, the Air Intake screen of the blower assembly will have to be remove& Replace after the check is made, Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 7.3.4e and 7.8a,b, as follows: 1. The exit terminals of a mechanical vent system shall be not less than 7 feet (2.13 m) above grade when located adjacent to public walkways, see Figure 23. 2. A venting system shall terminate at least 3 feet (91 cm) above any forced air inlet located within 10 feet (3.1 m), see Figure 23. 3. The venting system shall terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from or, 12 in. (30 cm) above any door, window or gravity air inlet into any building. The manufacturer also recommends that the vent termination should not be installed closer than 3 feet (91 cm) from an inside corner of an L shaped structure and not be less than 12 in. (30 cm) above grade. The vent shall terminate a minimum of 12" (30.5 cm) above expected snowfall level to prevent blockage of vent termination, see Figure 23. 4. In cold climates, it is recommended that vent termination not be mounted directly above or within 3 feet (91 cm) horizontally from an oil tank vent or gas meter to avoid potential freeze-up from condensation, see Figure 23. Plan the vent system layout so that proper clearances are maintained from plumbing and wiring. Vent pipes serving power vented appliances are classified by building codes as "vent connectors". Required clearances from combustible materials must be provided in accordance with information in this manual under FACTS TO CONSIDER ABOUT THE LOCATION and VENT TERMINAL INSTALLATIONS, and with the National Fuel Gas Code and local codes. VENT TERMINAL INSTALLATION 1. After the point of termination has been determined, use the cover plate as a template to mark the hole for the vent pipe to insert through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL. 2. If the Vent Terminal is being installed on the outside of a finished wall, it may be easier to mark both the inside and outside wall. Align the holes by drilling a hole through the center of the template from the inside through to the outside. The template can now be positioned on the outside wall using the drilled hole as a centering point for the template. 3. A) MASONRY SIDE WALLS Chisel an opening approximately one half inch larger than the marked circle. B) WOODEN SIDE WALLS Drill a pilot hole approximately one quarter inch outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately one quarter inch outside of the line. (This will allow the vent pipe to easily slide through the opening. The resulting gap will be covered up by the vent terminal cover plates.) Repeat this step on inside wall if necessary. 4. When the vent piping cannot pass through an outside wall at a height greater than or equal to 12" above the ground (or above snow accumulation level), then the installation can be modified as shown below. ii/ /// /11 I I GROUND ORSNOW _ ACCUMUALBAOTVIOEN LEVEL FIGURE 22. 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34

Breathing
Hazard
- Carbon
Monoxide
Gas
Install vent system
in accordance
with
codes.
Do
not
operate
water
heater
if flood
damaged
High altitude orifice
must be installed
for
operation
above7,700
feet (2,347
m).
Do not operate
if soot buildup.
Do not obstruct
water
heater
air intake
with insulating jackeL
Do not
place
chemical
vapor
emitting
products
near water heater.
• Gas
and
carbon
monoxide
detectors
are available.
Never
operate
the
heater
unless
it is
vented to the outdoors and has adequate
air
supply
to
avoid
risks
of
improper
operation, fire, explosion, or asphyxiation.
Make sure the flue baffle and flue restrictor
ring are properly aligned and inserted on
top
of
the
flue.
This
can
be
checked
through the dilution air
inlet
of the blower
assembly, For viewing, the Air Intake screen
of
the
blower assembly will
have to
be
remove& Replace after the check is made,
Breathing
carbon
monoxide
can cause
brain damage
or death.
Always
read and understand
instruction
manual.
The vent system must terminate so that proper clearances
are maintained
as cited
in local codes
or the current
edition
of the National
Fuel
Gas
Code, ANSI Z223.1/NFPA
54, 7.3.4e and 7.8a,b,
as follows:
1.
The exit terminals
of a mechanical
vent system
shall
be not less
than 7 feet
(2.13 m) above
grade
when
located
adjacent
to public
walkways,
see Figure 23.
2.
A venting
system shall terminate
at least 3 feet (91 cm) above any
forced air inlet located within
10 feet (3.1 m), see Figure 23.
3.
The venting system shall terminate
at least 4 feet (1.2 m) below, 4 feet
(1.2 m) horizontally
from or, 12 in. (30 cm) above any door, window
or gravity
air inlet into any building.
The manufacturer
also recommends
that the vent termination
should
not be installed
closer
than 3 feet (91 cm) from an inside corner
of
an L shaped
structure
and
not be less than
12 in. (30 cm) above
grade.
The vent shall terminate
a minimum
of 12" (30.5 cm) above expected
snowfall
level to prevent
blockage
of vent
termination,
see
Figure
23.
4.
In cold
climates,
it is recommended
that
vent termination
not be
mounted directly above or within 3 feet (91 cm) horizontally
from an oil
tank vent or gas meter to avoid potential freeze-up
from condensation,
see Figure
23.
Plan the vent system
layout
so that proper
clearances
are maintained
from plumbing
and wiring.
Vent pipes serving
power vented
appliances
are classified
by building
codes
as "vent
connectors".
Required
clearances
from
combustible
materials
must
be
provided
in accordance
with
information
in this
manual
under
FACTS
TO CONSIDER
ABOUT
THE
LOCATION
and
VENT
TERMINAL
INSTALLATIONS,
and with
the
National
Fuel Gas
Code and local codes.
VENT TERMINAL
INSTALLATION
1.
After
the point
of termination
has been determined,
use the cover
plate as a template
to mark the hole for the vent pipe to insert through
the wall. BEWARE
OF CONCEALED
WIRING AND
PIPING
INSIDE
OF WALL.
2.
3.
If the Vent Terminal is being installed
on the outside of a finished wall,
it may be easier to mark both the inside and outside
wall.
Align
the
holes by drilling
a hole through
the center
of the template
from the
inside through
to the outside.
The template
can now be positioned
on the outside wall using the drilled
hole as a centering
point for the
template.
A)
MASONRY
SIDE WALLS
Chisel an opening
approximately
one half inch larger than the marked
circle.
4.
B) WOODEN
SIDE WALLS
Drill a pilot hole approximately
one quarter inch outside of the marked
circle.
This pilot hole is used as a starting point for a saws-all or sabre
saw blade.
Cut around the marked
circle staying approximately
one
quarter
inch outside of the line.
(This will allow the vent
pipe to easily
slide through
the opening.
The resulting
gap will be covered
up by
the vent
terminal
cover
plates.)
Repeat
this step on inside wall if
necessary.
When
the
vent
piping
cannot
pass
through
an
outside
wall
at a
height greater than or equal to 12" above the ground
(or above snow
accumulation
level),
then the installation
can be modified
as shown
below.
///
///
///
///
ii/
///
/11
ABOVE
I
I
GROUND ORSNOW
_
ACCUMULATIONLEVEL
FIGURE
22.
19