Kenmore 7853 Installation Instructions - Page 5

Read these, electrical, connection, details, first, connect, electricity, to range.

Page 5 highlights

Fig. 4d Fig. 4e the 1/2" flare union adapter with an adjustable wrench before tightening the gas supply fitting and!or appliance conduit (Refer to Fig. 4e). d) Install flare union adapter to external manual shut-off valve. e) Attach appliance conduit to flare union on shut-off valve. t) Make sure service shut-off valve on pressure regulator is in the "ON" position (See Fig. 4f). g) Check for leaks. Turn the gas supply on to the range and use a liquid leak detector at all joints and conduits to check for leaks in the system. Do not use flame to check for gas leaks. Checking Manifold Gas Pressure Disconnect the range and its individual shut-off valve from the gas supply piping system during any pressure testing of that system at test pressures greater than 14" of water column pressure (approximately 1/2" psig). The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 14" of water column pressure (approximately 1!2" psig). if it should be necessary to check the manifold gas pressure, connect manometer (water gauge) or other pressure device to thetopburner right rearorifice. Usinga rubberhosewith inside diameter of approximately 1/4," hold tubing down tight over orifice. Turn burnervalveon. For an accurate pressure check have at least two (2) other top burners burning. Be sure the gas supply (inlet) pressure is at least one inchabove specified range manifold pressure. The gas supply pressure should never be over 14" water column. When properly adjusted for Natural Gas the manifold pressure is 4." (For LP/Propane Gas the manifold pressure is 10.") Fig. 4f DO NOT allow regulator to turn on pipe when tightening fittings. a) install an external manual gas shut-offvaJve to gas supply line in an accessible location outside of the range. Be sure you know where and how to shut off the gas supply to the range. b) Install 1/2"flareunionadaptertopressureregulatorusing NO MORETHAN 15ftJlbs. of torque NOTE: Be sure to stabilize the left side of the pressure regulator with adjustable wrench before tightening ANY fittings to the pressure regulator (Refer to Fig. 4d). c) Tighten the gas supply fitting and/or appliance conduit to flare union on the right side of the pressure regulator using NO MORE THAN 15ft./lbs. of torque. Be sure to stabilize 5. Read these electrical connection details first then connect electricity to range. Before servicing, disconnect electrical supply at circuit breaker, fuse or power cord. Electric Requirements: A dedicated, properly grounded and polarized branch circuit protected by a 15 amp. circuit breaker or time delay fuse. See serial plate for proper voltage. Extension Cord Precautions: Because of potential safety hazards under certain conditions, we strongly recommend against the use of any extension cord. However, if you still elect to use an extension cord, it is absolutely necessary that it be a UL listed 3-wire grounding type appliance extension cord and that the current carrying rating of the cord in amperes be equivalent to or greater than the branch circuit rating. Such extension cords are obtainable through your local service organization.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

Fig. 4d
Fig. 4e
Fig. 4f
d)
e)
t)
g)
the 1/2" flare
union adapter
with an adjustable
wrench
before tightening
the gas supply fitting and!or appliance
conduit (Refer to Fig. 4e).
Install flare union adapter to external manual shut-off valve.
Attach appliance conduit to flare union on shut-off valve.
Make sure service shut-off
valve on
pressure
regulator
is
in the "ON"
position
(See Fig. 4f).
Check for leaks. Turn the gas supply on to the range and
use a liquid
leak detector
at all joints
and conduits
to
check for leaks
in
the system.
Do
not
use
flame
to
check
for
gas
leaks.
Checking
Manifold
Gas
Pressure
Disconnect the range and
its individual
shut-off valve from the
gas supply piping system during any pressure testing of that
system
at test pressures
greater than 14" of water column
pressure (approximately
1/2" psig).
The appliance
must be
isolated
from the gas supply piping
system by closing
its individual
manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 14" of water column pressure
(approximately
1!2" psig).
if it
should be necessary to check the manifold gas pressure,
connect manometer (water gauge) or other pressure device to
thetopburner
right rearorifice.
Usinga rubberhosewith
inside
diameter
of approximately
1/4," hold tubing down tight over
orifice. Turn burnervalveon.
DO NOT allow
regulator
to
turn
on pipe
when tightening
fittings.
a)
install an external manual gas shut-offvaJve to gas supply
line in an accessible location outside of the range. Be sure
you know where and how to shut off the gas supply to the
range.
b)
Install 1/2"flareunionadaptertopressureregulatorusing
NO MORETHAN
15ftJlbs.
of torque
NOTE:
Be sure to stabilize
the left side of the pressure
regulator with adjustable wrench before tightening
ANY
fittings to the pressure regulator (Refer to Fig. 4d).
c)
Tighten the gas supply fitting and/or appliance conduit to
flare union on the right side of the pressure regulator using
NO MORE THAN 15ft./lbs.
of torque. Be sure to stabilize
For an accurate pressure check have at least two (2) other top
burners burning. Be sure the gas supply (inlet) pressure
is
at
least one
inch
above specified range manifold pressure. The
gas supply pressure should never be over 14" water column.
When properly adjusted for Natural Gas the manifold pressure
is
4." (For LP/Propane
Gas the manifold pressure
is
10.")
5. Read these
electrical
connection
details
first
then
connect
electricity
to range.
Before
servicing,
disconnect
electrical
supply
at circuit
breaker,
fuse or
power
cord.
Electric
Requirements:
A dedicated,
properly grounded
and
polarized branch circuit protected by a 15 amp. circuit breaker
or time delay fuse. See serial plate for proper voltage.
Extension Cord Precautions:
Because of potential safety hazards under certain conditions,
we strongly
recommend
against
the use of any extension
cord. However, if you still elect to use an extension cord, it is
absolutely
necessary
that it be a UL listed 3-wire grounding
type appliance
extension cord and that the current carrying
rating of the cord in amperes be equivalent
to or greater than
the branch circuit rating. Such extension cords are obtainable
through your local service organization.