Installing the Cooktop Electrical Connections Important Safety Instructions • Be sure the cooktop is installed and grounded properly by a qualified installer or service technician. • This cooktop must be electrically grounded in accordance with local codes or, in their absence, with the National Electrical Code ANSI/NFPA No. 70, latest edition in the United States. WARNING • The electrical power to the cooktop must be shut off while line connections are being made. Failure to do so could result in serious injury or death. Providing the Electrical Connection • Install the junction box under the cabinet and run 120/240 or 120/208 Volt, AC wire from the main circuit panel. NOTE • DO NOT connect the wire to the circuit panel at this time. Electrical Requirements Observe all governing codes and local ordinances 1 A 3-wire or 4-wire single-phase 120/240 or 120/208 Volt, 60 Hz AC-only electrical supply is required on a separate circuit fused on both sides of the line (time-delay fuse or circuit breaker is recommended). DO NOT fuse neutral. The fuse size must not exceed the circuit rating of the appliance specified on the nameplate. 2 36" induction cooktop can consume up to 10650 W at 240 VAC. A 50 Amp circuit breaker with wire guage #8 AWG must be used. WARNING • Do not use an extension cord with this appliance. Such use may result in a fire, electrical shock, or other personal injury. INSTALLATION 13 NOTE • Wire sizes and connections must conform to the fuse size and rating of the appliance in accordance with the National Electrical Code ANSI/NFPA No. 70, latest edition, and local codes and ordinances. 3 The appliance should be connected to the fused disconnect (or circuit breaker) box through flexible armored or nonmetallic sheathed cable. The flexible armored cable extending from this appliance should be connected directly to the grounded junction box. The junction box should be located as shown in Dimensions and Clearances with as much slack as possible remaining in the cable between the box and the appliance, so it can be moved if servicing is ever necessary. 4 A suitable strain relief must be provided to attach the flexible armored cable to the junction box. Electrical Connection Connect the flexible armored cable that extends from the surface unit to the junction box using a suitable strain relief at the point the armored cable enters the junction box. Then make the electrical connection as follows. Electrical ground is required on this appliance. This appliance is manufactured with a supply wire and a frame-connected green or bare copper grounding wire. NOTE TO ELECTRICIAN: • The armored cable leads supplied with the appliance are UL-listed for connection to larger gauge household wiring. The insulation of the leads is rated at temperatures much higher than the temperature rating of household wiring. The current-carrying capacity of the conductor wire is governed by the temperature rating of the insulation around the wire, rather than the wire gauge alone. WARNING • DO NOT ground to a gas supply pipe. DO NOT connect to electrical power supply until appliance is permanently grounded. Connect the ground wire before turning on the power. ENGLISH

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

13
INSTALLATION
ENGLISH
Installing the Cooktop
Electrical Connections
Important Safety Instructions
Be sure the cooktop is installed and grounded
properly by a qualified installer or service
technician.
This cooktop must be electrically grounded in
accordance with local codes or, in their absence,
with the National Electrical Code ANSI/NFPA No.
70, latest edition in the United States.
WARNING
The electrical power to the cooktop must be shut
off while line connections are being made.
Failure to do so could result in serious injury or
death.
Providing the Electrical Connection
Install the junction box under the cabinet and
run 120/240 or 120/208 Volt, AC wire from the
main circuit panel.
NOTE
DO NOT connect the wire to the circuit panel at
this time.
Electrical Requirements
Observe all governing codes and local ordinances
1
A 3-wire or 4-wire single-phase 120/240 or
120/208 Volt, 60 Hz AC-only electrical supply is
required on a separate circuit fused on both
sides of the line (time-delay fuse or circuit
breaker is recommended). DO NOT fuse
neutral. The fuse size must not exceed the
circuit rating of the appliance specified on the
nameplate.
2
36" induction cooktop can consume up to
10650 W at 240 VAC. A 50 Amp circuit breaker
with wire guage #8 AWG must be used.
WARNING
Do not use an extension cord with this
appliance. Such use may result in a fire, electrical
shock, or other personal injury.
NOTE
Wire sizes and connections must conform to the
fuse size and rating of the appliance in
accordance with the National Electrical Code
ANSI/NFPA No. 70, latest edition, and local codes
and ordinances.
3
The appliance should be connected to the
fused disconnect (or circuit breaker) box
through flexible armored or nonmetallic
sheathed cable. The flexible armored cable
extending from this appliance should be
connected directly to the grounded junction
box. The junction box should be located as
shown in
Dimensions and Clearances
with
as much slack as possible remaining in the
cable between the box and the appliance, so it
can be moved if servicing is ever necessary.
4
A suitable strain relief must be provided to
attach the flexible armored cable to the
junction box.
Electrical Connection
Connect the flexible armored cable that extends
from the surface unit to the junction box using a
suitable strain relief at the point the armored cable
enters the junction box. Then make the electrical
connection as follows.
Electrical ground is required on this appliance.
This appliance is manufactured with a supply wire
and a frame-connected green or bare copper
grounding wire.
NOTE
TO ELECTRICIAN:
The armored cable leads supplied with the
appliance are UL-listed for connection to larger
gauge household wiring. The insulation of the
leads is rated at temperatures much higher than
the temperature rating of household wiring. The
current-carrying capacity of the conductor wire
is governed by the temperature rating of the
insulation around the wire, rather than the wire
gauge alone.
WARNING
DO NOT ground to a gas supply pipe. DO NOT
connect to electrical power supply until
appliance is permanently grounded. Connect the
ground wire before turning on the power.