LG LP091HEM Owner's Manual (English) - Page 19

Front Desk Control, Remote Wall Thermostat, Remote/local Control, Energy Saver

Page 19 highlights

ENGLISH Control Locations • REMOTE/LOCAL CONTROL When remote/local switch #1 is on, it allow the unit to operate by the control of Remote Wall Thermostat. The unit control by knobs are not available. • ENERGY SAVER The energy saver switch #2 is on. This switch is set at continuous fan to provide continuous fan operation in cool or heat modes. When the switch is off the continuous fan allows continuous circulation of room air and make the more balanced temperature of the room. When the switch is on the fan is on or off with the compressor or with the heater. • FRONT DESK CONTROL When the pair wire is connected to the connector LOand LI, the unit can be turned ON or OFF with a switch located at the Front Desk Control panel. When the front desk switch is ON, the fan operate according to the condition of setting without working compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls. Wire # AWG #22 #20 #18 #16 Maximum Length 600ft(180m) 900ft(270m) 1500ft(450m) 2000ft(610m) LO LI GL GH O W Y R C Front Desk Switch Note:The following figures show wiring schematics for heat pump and straight cool units with electric heat, respectively. Wiring Schematic for Remote Heat Pump • REMOTE WALL THERMOSTAT When the wires are connected, the unit will be controlled by a remote wall thermostat. The thermostat connections supply the 24 Volt AC. When you install the digital / electronic thermostat, you must set it to the 24 Volt AC. See the installation Instruction in this manual for the Remote Wall Thermostat. 24 Volt-N 24 Volt-L Compressor Heater Reversing Valve High Fan Low Fan LO LI GL GH O W Y R C (Molex Housing Spec 396-09V) Wiring Schematic for Straight Cool Unit. Owner's Manual 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27

Control Locations
Owner’s Manual
19
ENGLISH
(Molex Housing Spec 396-09V)
FRONT DESK CONTROL
When the pair wire is connected to the connector LOand LI, the unit can be turned ON or OFF with a switch
located at the Front Desk Control panel. When the front desk switch is ON, the fan operate according to the
condition of setting without working compressor and heater.When the front desk switch is OFF, the unit can
operate according to the setting of controls.
REMOTE WALL THERMOSTAT
When the wires are connected, the unit will be
controlled by a remote wall thermostat.
The thermostat connections supply the 24 Volt AC.
When you install the digital / electronic thermostat,
you must set it to the 24 Volt AC. See the installation
Instruction in this manual for the Remote Wall
Thermostat.
REMOTE/LOCAL CONTROL
When remote/local switch #1 is on, it allow the unit to operate by the control of Remote Wall Thermostat.
The unit control by knobs are not available.
ENERGY SAVER
The energy saver switch #2 is on.This switch is set at continuous fan to provide continuous fan operation in
cool or heat modes. When the switch is off the continuous fan allows continuous circulation of room air and
make the more balanced temperature of the room. When the switch is on the fan is on or off with the
compressor or with the heater.
Wire # AWG
Maximum Length
#22
600ft(180m)
#20
900ft(270m)
#18
1500ft(450m)
#16
2000ft(610m)
GL GH
O
W
Y
R
C
LO LI
Front Desk Switch
LO LI
GL GH
O
W
Y
R
C
Low Fan
High Fan
Reversing Valve
Heater
Compressor
24 Volt-L
24 Volt-N
Wiring Schematic for
Remote Heat Pump
Wiring Schematic for
Straight Cool Unit.
Note:
The following figures show
wiring schematics for heat pump
and straight cool units with electric
heat, respectively.