LG LW6019ER Owners Manual - Page 18

Problem, Possible Cause, Solutions

Page 18 highlights

18 TROUBLESHOOTING Problem Air conditioner does not start. Possible Cause The air conditioner is unplugged. The fuse is blown/circuit breaker is tripped. Power failure. The current interrupter device is tripped. Solutions Make sure the air conditioner plug is pushed completely into the outlet. Check the house fuse/circuit breaker box and replace the fuse or reset the breaker. If power failure occurs, turn the mode control to off. When power is restored, wait 3 minutes to restart the air conditioner to prevent tripping of the compressor overload. Press the RESET button located on the power cord plug. If the RESET button will not stay engaged, discontinue use of the air The temp control may not be set correctly. service technician. Make sure there are no curtains, blinds, or furniture blocking the front of the air conditioner. Set the desired temperature to a level lower than the current temperature. Air conditioner does not cool as it should. The room may have been hot. Cold air is escaping. Cooling coils have iced up. weeks. See the 'MAINTENANCE' section. turned on, you need to allow time for the room to cool down. registers and cold air returns. See 'Air conditioner freezing up' below. Air conditioner freezing up. Water drips outside. The cooling coils are iced over. Hot, humid weather. obstruct the air conditioner from properly cooling the room. Set the mode control at High Fan or High Cool. This is normal.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

18
TROUBLESHOOTING
Problem
Possible Cause
Solutions
Air conditioner
does not start.
The air conditioner is unplugged.
Make sure the air conditioner plug
is pushed completely into the outlet.
The fuse is blown/circuit breaker
is tripped.
Check the house fuse/circuit
breaker box and replace the fuse or
reset the breaker.
Power failure.
If power failure occurs, turn the
mode control to off. When power is
restored, wait 3 minutes to restart
the air conditioner to prevent
tripping of the compressor overload.
The current interrupter device is
tripped.
Press the
RESET
button located
on the power cord plug. If the
RESET
button will not stay
engaged, discontinue use of the air
service technician.
Air conditioner
does not cool as it
should.
Make sure there are no curtains,
blinds, or furniture blocking the front
of the air conditioner.
The temp control may not be set
correctly.
Set the desired temperature to
a level lower than the current
temperature.
weeks. See the 'MAINTENANCE'
section.
The room may have been hot.
turned on, you need to allow time
for the room to cool down.
Cold air is escaping.
registers and cold air returns.
Cooling coils have iced up.
See 'Air conditioner freezing up'
below.
Air conditioner
freezing up.
The cooling coils are iced over.
obstruct the air conditioner from
properly cooling the room. Set the
mode control at
High Fan
or
High
Cool
.
Water drips
outside.
Hot, humid weather.
This is normal.