Lantronix EDCA-DIO-01 Quick Start Guide EDCA-DIO-01 Enclosure Door Contact Alarm Quick Start Guide Note: See the Install Guide for important information. Product Description The Lantronix EDCA-DIO-01 Enclosure Door Contact Alarm adds an additional level of security to applications by monitoring the status of the door on equipment enclosures. The EDCA-DIO-01 inserts power into any 12V Digital Input (DI) application by making it active. Specifications IEEE, IETF, Safety Compliance Regulatory Compliance - Emission Regulatory Compliance - Immunity Power Consumption Power Source Power Output Dimensions Weight Environment Warranty N/A EN 55032 EN 55024 1.2W (100mA at 12V out max.) 20-60 VDC 12VDC +/- 10% 2.2" x 2" x 7/8" (6.2 x 5 x 2.2 cm) 0.2 Lb. (0.09 Kg.) Oper. Temp: -25 to +75° C. Storage: -40 to +85° C. Altitude: 0-10,000 ft. Oper. Humidity: 5% to 95% (non-condensing) Lifetime Installation Package Contents: Carefully unpack the EDCA-DIO-01 and verify you have received one EDCA-DIO-01, one printed Quick Start Guide, DIN Rail Clip and one Documentation Postcard. DIN Rail Clip Installation: Attach and tighten the DIN rail clip on the threaded stud until it is secured and aligned properly. Wall Mount Plate Installation (Optional): 1. Attach the Wall Mount Plate to the EDCA-DIO-01 using the two provided screws. 2. Attach the Wall Mount Plate to the enclosure wall using Velcro, industrial tape, nuts and bolts, super glue, rivets, etc. (not provided). EDCA-DIO-01Installation The EDCA-DIO-01 requires power and can be powered by the same power supply providing power to the Lantronix Ethernet switch in the cabinet. The power port (marked DC Input) is a 2-wire Terminal Block supporting 20 - 60 VDC. The DI ports must also be 2-wire terminal blocks on the Lantronix Ethernet switch. Lantronix sells as an optional accessory a universal mechanical door contact closure switch that works with a variety of enclosures. However, your cabinet manufacturer may provide a door closure contact switch. The switch requires wire connection terminals. 33796 Rev. C https://www.lantronix.com/ Page 1 of 2

  • 1
  • 2

Lantronix
EDCA-DIO-01 Quick Start Guide
33796 Rev. C
Page
1
of
2
EDCA-DIO-01
Enclosure Door Contact Alarm
Quick Start Guide
Note
: See the Install Guide for important information.
Product Description
The Lantronix EDCA-DIO-01 Enclosure Door Contact Alarm adds an additional level of security to applications by
monitoring the status of the door on equipment enclosures. The EDCA-DIO-01 inserts power into any 12V Digital Input
(DI) application by making it active.
Specifications
IEEE, IETF, Safety Compliance
N/A
Regulatory Compliance - Emission
EN 55032
Regulatory Compliance - Immunity
EN 55024
Power Consumption
1.2W (100mA at 12V out max.)
Power Source
20-60 VDC
Power Output
12VDC +/-
10%
Dimensions
2.2“ x 2” x 7/8” (6.2 x 5 x 2.2 cm)
Weight
0.2 Lb. (0.09 Kg.)
Environment
Oper. Temp: -25 to +75° C. Storage: -40 to +85° C. Altitude: 0-10,000 ft. Oper. Humidity: 5% to 95% (non-condensing)
Warranty
Lifetime
Installation
Package Contents
: Carefully unpack the EDCA-DIO-01 and verify you have received one EDCA-DIO-01, one printed Quick Start Guide, DIN Rail Clip and one
Documentation Postcard.
DIN Rail Clip Installation
: Attach and tighten the DIN rail clip on the threaded stud until it is secured and aligned properly.
Wall Mount Plate Installation (Optional)
:
1.
Attach the Wall Mount Plate to the EDCA-DIO-01 using the two provided screws.
2.
Attach the Wall Mount Plate to
the enclosure wall using Velcro, industrial tape, nuts and bolts, super glue, rivets, etc. (not provided).
EDCA-DIO-01Installation
The EDCA-DIO-01 requires power and can be powered by the same power supply providing power to the Lantronix Ethernet switch in the cabinet.
The power port (marked DC Input) is a 2-wire Terminal Block supporting 20 - 60 VDC. The DI ports must also be 2-wire terminal blocks on the Lantronix Ethernet
switch. Lantronix sells as an optional accessory a universal mechanical door contact closure switch that works with a variety of enclosures.
However, your cabinet
manufacturer may provide a door closure contact switch. The switch requires wire connection terminals.