RS-485 Configuration

Page 41 highlights

MSS User Guide 4: Configuration RS-485 Configuration Note: This section applies to MSS models MSS-VIA and MSS4 only. The RS-485 standard allows a serial connection to be shared like a "party line." As many as 32 devices can share the multidrop network. Typically, one device is the master and the other devices are slaves. There are a few important things to note about RS-485 networking with the MSS. ‹ MSS-VIA allows for a serial connection on one port. MSS4 allows for a serial connection on all four ports; specify the port when entering RS-485 commands. ‹ The MSS can be used in either two-wire or four-wire mode. Refer to the following sections to determine which mode to use. ‹ The maximum RS-485 network cabling length (without repeaters) is 4,000 feet. Lantronix recommends the use of shielded twisted-pair cabling. Note: A large number and variety of protocols run over RS-485. However, the MSS does not convert or interpret serial data. It only moves data between serial and Ethernet. Any RS-485 protocol will have to be implemented by host software either on the end device or running internally using the Software Development Kit (SDK) . See 7:Pinouts for information about the RS-485 DB25 connector. To enable RS-485 mode on the MSS, enter the Change RS485 Enabled command. RS232 mode is enabled by default. Figure 4-19: Enabling RS-485 Mode for MSS4 Local> CHANGE RS485 PORT 2 ENABLED Figure 4-20. Enabling RS-485 Mode for MSS-VIA Local> CHANGE RS485 ENABLED Two-Wire Mode In two-wire mode, the MSS operates in half duplex: one pair of wires shares transmit and receive signals, and an optional third wire can be used for shield/ground. The main advantage of using two-wire mode is reduced cabling costs. Figure 4-21: Example Two-Wire Mode Network On a two-wire RS-485 network, the MSS must turn its transmitter on when it is ready to send data and then off a certain period of time after the data has been sent so that the 4-8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81

MSS User Guide
4:
Configuration
4-8
RS-485 Configuration
Note:
This section applies to MSS models MSS-VIA and MSS4 only.
The RS-485 standard allows a serial connection to be shared like a "party line." As many
as 32 devices can share the multidrop network. Typically, one device is the master and
the other devices are slaves. There are a few important things to note about RS-485
networking with the MSS.
MSS-VIA allows for a serial connection on one port.
MSS4 allows for a serial
connection on all four ports; specify the port when entering RS-485 commands.
The MSS can be used in either two-wire or four-wire mode. Refer to the following
sections to determine which mode to use.
The maximum RS-485 network cabling length (without repeaters) is 4,000 feet.
Lantronix recommends the use of shielded twisted-pair cabling.
Note:
A large number and variety of protocols run over RS-485. However, the MSS does
not convert or interpret serial data. It only moves data between serial and Ethernet. Any
RS-485 protocol will have to be implemented by host software either on the end device or
running internally using the Software Development Kit (SDK) . See
7:Pinouts
for
information about the RS-485 DB25 connector.
To enable RS-485 mode on the MSS, enter the
Change RS485 Enabled
command. RS-
232 mode is enabled by default.
Figure
4-19:
Enabling RS-485 Mode for MSS4
Local> CHANGE RS485 PORT 2 ENABLED
Figure
4-20. Enabling RS-485 Mode for MSS-VIA
Local> CHANGE RS485
ENABLED
Two-Wire Mode
In two-wire mode, the MSS operates in half duplex: one pair of wires shares transmit and
receive signals, and an optional third wire can be used for shield/ground. The main
advantage of using two-wire mode is reduced cabling costs.
Figure
4-21:
Example Two-Wire Mode Network
On a two-wire RS-485 network, the MSS must turn its transmitter on when it is ready to
send data and then off a certain period of time after the data has been sent so that the