Location Of Your Maytag Appliance Locate this appliance away from combustible materials such as window curtains and combustible wall decorations. Minimum horizontal clearance between the edge of the appliance and combustible construction extending from the cooking surface to 18² (45.72 cm) above the cooking surface is: 1.0² (2.54 cm) at rear 6² (15.24 cm) at sides (Dimensions apply to both 30² and 36² wide models). Important Preparation Suggestions 1. Chamfer all exposed edges of decorative laminate to prevent damage from chipping. 2. Radius corners of cutout and file to insure smooth edges and prevent corner cracking. Recommend 1/4² or 3/8² diameter drill in each corner. 3. Rough edges, inside corners which have not been rounded and forced fits can contribute to cracking of the countertop laminate. 4. Countertop must be supported within 3² (7.62 cm) of cutout. 1.0² 2.54 cm FIGURE 1 18² 45.72 cm 6² 15.24 cm Preparation Of Countertop The countertop cutout must be prepared according to the illustration on page 1 of these instructions. CAUTION: Cutout dimensions are critical. Dimensions must be measured and cut accurately to within + 1/16² (.159 cm) to ensure proper fit. Installing Cabinetry Over Your Maytag Cooktop A = 30² (76.2 cm) minimum vertical clearance between cooking surface and construction above the appliance. This clearance may be reduced to not less than 24 inches (60.96 cm) by protecting the underside of the combustible material or metal cabinet above the cooking surface with not less than 1/4 inch (.635 cm) insulating millboard covered with sheet metal not less than 0.0122 inch thick. FIGURE 2 B = 13² (33.02 cm) maximum depth of cabinets installed above cooktop. Avoid use of cabinets above cooktop for storage space to eliminate associated potential hazards such as reaching over open flames. Required Adjustments At Time Of Installation The installation of this appliance must conform with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code ANSI Z223.1 USA or current CAN/CGA-B149 INSTALLATION CODE. V This appliance was manufactured for use with Natural Gas. If LP gas is the fuel of choice, follow the conversion to LP procedure found in the installation instructions. V Test all external connections for gas leaks. Never test for gas leaks with an open flame. V Test all electrical connections. 2

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33

2
Location Of Your Maytag
Appliance
Locate this appliance away from combustible materials
such as window curtains and combustible wall
decorations.
Minimum horizontal clearance between the edge of the
appliance and combustible construction extending from
the cooking surface to 18
±
(45.72 cm) above the cooking
surface is:
1.0
±
(2.54 cm) at rear
6
±
(15.24 cm) at sides
(Dimensions apply to both 30
±
and 36
±
wide models).
FIGURE 1
Preparation Of Countertop
The countertop cutout must be prepared according to the
illustration on page 1 of these instructions.
CAUTION:
Cutout dimensions are critical. Dimensions
must be measured and cut accurately to within +
1/16
±
(.159 cm) to ensure proper fit.
Important Preparation
Suggestions
1. Chamfer all exposed edges of decorative laminate to
prevent damage from chipping.
2.
Radius corners of cutout and file to insure smooth
edges and prevent corner cracking. Recommend
1/4
±
or 3/8
±
diameter drill in each corner.
3. Rough edges, inside corners which have not been
rounded and forced fits can contribute to cracking of
the countertop laminate.
4. Countertop must be supported within 3
±
(7.62 cm) of
cutout.
Installing Cabinetry Over Your
Maytag Cooktop
A = 30
±
(76.2 cm) minimum
vertical clearance
between cooking surface
and construction above
the appliance. This
clearance may be
reduced to not less than
24 inches (60.96 cm) by
protecting the underside
of the combustible
material or metal cabinet
above the cooking
surface with not less than
1/4 inch (.635 cm)
insulating millboard
covered with sheet metal
not less than 0.0122 inch
thick.
B = 13
±
(33.02 cm) maximum depth of cabinets installed
above cooktop.
Avoid use of cabinets above cooktop for storage space to
eliminate associated potential hazards such as reaching
over open flames.
FIGURE 2
Required Adjustments At Time Of Installation
The installation of this appliance must conform with local codes, or in the absence of local codes, with
the latest edition of the National Fuel Gas Code ANSI Z223.1 USA or current CAN/CGA-B149
INSTALLATION CODE.
V
This appliance was manufactured for use with Natural Gas. If LP gas is the fuel of choice, follow
the conversion to LP procedure found in the installation instructions.
V
Test all external connections for gas leaks. Never test for gas leaks with an open flame.
V
Test all electrical connections.
1.0
²
2.54 cm
6
²
15.24 cm
18
²
45.72 cm