Sanyo SRR-72GD-MED Instruction Manual - Page 16
Default, Settings
View all Sanyo SRR-72GD-MED manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
DEFAULT SETTINGS Refrigerator The setted temp. : 4°C standard Cooling rate : 40 min from ambient 25t to the set temp. of 4°C Automatic Defrosting Period : Every 8 hours Defrosting duratio : 10 min standard. If the evaporator coil temperature reaches to 14t, defrosting will be shut down. Freezer The setted temp. : -20°C standard Cooling rate : 70 min from ambient 25°C to the set temp. of -20°C Automatic Defrosting Period : Every 6 hours Defrosting duratio : 30 min standard. The particular metter Alram Function : *The alarm is preset at ±5 degrees C. It will be working if the inside temperature goes up and down for around set point. You can turn on or off the alarm, by using the switch on the side of the controller. *The model SRR-72GD-MED should be turned on alram when the both of inside temperature goes down to setting temperature. 16