Electrical Installation All model ovens on the front cover are dual rated, designed to be connected to either 208/240V AC, 60 Hz, 4 wire, single-phase power supply. Model ME301JP, ME301JS, MED271JS, MED301JS, MED301JP, POD301J ME302JP, ME302JS, MED272JS, MED302JS, MED302JP, PODC302J MEDMC301JS, MEDMC301JP, MEDMCW71JS, MEDMCW31JP, MEDMCW31JS, PODM301J, PODMW301J Circuit Required 30 AMP 40 AMP 50 AMP The electrical supply should be a 4-wire single-phase AC. Install a suitable conduit box (not furnished). An appropriately-sized, UL-listed conduit connector must be used to correctly attach the conduit to the junction box. NOTICE: Local Codes may vary; installation, electrical connections and grounding must comply with all applicable local codes. If local codes permit grounding through the electrical supply neutral, connect both the white neutral wire and the bare ground wire from the oven to the white neutral electrical supply wire. Electrical Connection The four-wire connection is preferred, but where local codes permit, the three wire connection is also acceptable. Four-wire Connection 1 Cable from power supply 2 White wires 3 Black wires 4 U.L.-listed conduit connector 5 Cable from oven 6 Bare or green wires 7 Red wires 8 Junction box ▯ Connect the red oven wire to the red electrical supply wire (hot wire). ▯ Connect the black oven wire to the black electrical supply wire (hot wire). ▯ Connect the white neutral oven wire to the white neutral (not bare ground) electrical supply wire. ▯ Connect the oven bare ground wire to the bare (or green) electrical supply ground wire. 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

8
Electrical Installation
All model ovens on the front cover are dual rated,
designed to be connected to either 208/240V AC,
60 Hz, 4 wire, single-phase power supply.
The electrical supply should be a 4-wire single-phase AC.
Install a suitable conduit box (not furnished). An
appropriately-sized, UL-listed conduit connector must be
used to correctly attach the conduit to the junction box.
NOTICE:
Local Codes may vary; installation, electrical
connections and grounding must comply with all
applicable local codes.
If local codes permit grounding through the electrical
supply neutral, connect both the white neutral wire and
the bare ground wire from the oven to the white neutral
electrical supply wire.
Electrical Connection
The four-wire connection is preferred, but where local
codes permit, the three wire connection is also
acceptable.
Four-wire Connection
Connect the red oven wire to the red electrical supply
wire (hot wire).
Connect the black oven wire to the black electrical
supply wire (hot wire).
Connect the white neutral oven wire to the white
neutral (not bare ground) electrical supply wire.
Connect the oven bare ground wire to the bare (or
green) electrical supply ground wire.
Model
Circuit Required
ME301JP,
ME301JS,
MED271JS,
MED301JS,
MED301JP,
POD301J
30 AMP
ME302JP,
ME302JS,
MED272JS,
MED302JS,
MED302JP,
PODC302J
40 AMP
MEDMC301JS,
MEDMC301JP,
MEDMCW71JS,
MEDMCW31JP,
MEDMCW31JS,
PODM301J,
PODMW301J
50 AMP
1
Cable from power supply
2
White wires
3
Black wires
4
U.L.-listed conduit connector
5
Cable from oven
6
Bare or green wires
7
Red wires
8
Junction box
°
±