Thermador PRG364JDG Installation Manual - Page 5

Step 1: Ventilation Requirements - microwave

Page 5 highlights

Tools Needed (2) 1/2" wrenches 1/8" (3.17mm) drill bit 3/16" (4.76mm) drill bit 12" Adjustable wrench Hand or electric drill Tape measure Phillips & flathead screwdrivers Marking instrument Level Furniture dolly T-20 Torx screwdriver Protective gloves Items Not Included Drywall/Concrete Anchors Pipe Compound/Tape Rope/Twine 3/4" (19mm) Flex Line (2) NPT Flare Adapters Step 1: Ventilation Requirements It is strongly recommended that a suitable exhaust hood be installed above the range. Downdraft ventilation should not be used. The table below indicates the ventilation hood options and blower capacity guidelines that are recommended for use with all THERMADOR® ranges. Do not install a microwave oven/ventilator combination above the range as these type of units do not provide the proper ventilation and are not suitable for use with the range. NOTICE: Most range hoods contain combustible components which must be considered when planning the installation. 1. Select Hood and Blower Models: • For wall installations, the hood width must, at a minimum, equal the width of the range. Where space permits, a hood larger in width than the range may be desirable for improved ventilation performance. • For island installations, the hood width should overhang the range by a minimum of 3" (76mm) on each side. 2. Hood Placement: • For best smoke elimination, the lower edge of the hood should be installed 30" (762mm) above the range cooking surface. Use a 36" (914mm) minimum clearance if the hood contains any combustible materials such as a wood covering (Figure 1 on page 5). 3. Consider Make-Up Air: • Due to the high volume of ventilation air, a source of outside replacement air is recommended. This is particularly important for tightly sealed and insulated homes. • A qualified heating and ventilating contractor should be consulted. Important: Ventilation hoods and blowers are designed for use with single wall ducting. However, some local building codes or inspectors may require double wall ducting. Consult local building codes and/or local agencies before starting to assure that hood and duct installation will meet local requirements. Range Width Range Top Configuration Cubic Feet per Minute (min requirement) Ventilation Options 4 burners with griddle 36" 6 burners 800 (cfm) 1100 (cfm) 36" or 42" Pro Wall Hood 36" Custom Insert w/ optional blower 42" or 48" Island Hood w/ optional blower 48" 6 burners with griddle 1200 (cfm) 48" or 54" Pro Wall Hood 48" Custom Insert w/ optional blower Important Notes: It is recommended that a THERMADOR PROFESSIONAL® wall or island hood or custom insert is used with THERMADOR PROFESSIONAL® Ranges. Refer to www.thermador.com for a complete selection of Professional Ventilation options, Blowers, and Accessories. * For high output gas ranges (60,000 BTU or greater), the minimum of one (1) CFM of ventilation per 100 BTU is recommended. If the range has a griddle, add 200 CFM to the estimated blower capacity. Additional blower capacity may be required for longer duct runs. For island applications, it is recommended to use a hood width that exceeds the width of the range by 6" (152mm), overlapping the range by a minimum of 3" (76mm) on each end. CFM = "cubic feet per minute" (standard blower capacity rating). English 3

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96

English 3
Step 1: Ventilation Requirements
It is
strongly
recommended that a suitable exhaust
hood
be
installed
above
the
range.
Downdraft
ventilation should not be used. The table below
indicates the ventilation hood options and blower
capacity guidelines that are recommended for use with
all THERMADOR
®
ranges.
Do not install a microwave oven/ventilator combination
above the range as these type of units do not provide
the proper ventilation and are not suitable for use with
the range.
NOTICE:
Most range hoods contain combustible components which
must be considered when planning the installation.
1.
Select Hood and Blower Models:
For wall installations, the hood width must, at a
minimum, equal the width of the range. Where space
permits, a hood larger in width than the range may be
desirable for improved ventilation performance.
For island installations, the hood width should
overhang the range by a minimum of 3" (76mm) on
each side.
2.
Hood Placement:
For best smoke elimination, the lower edge of the hood
should be installed 30" (762mm) above the range
cooking surface. Use a 36" (914mm) minimum
clearance if the hood contains any combustible
materials such as a wood covering (Figure 1 on
page 5).
3.
Consider Make-Up Air:
Due to the high volume of ventilation air, a source of
outside replacement air is recommended. This is
particularly important for tightly sealed and insulated
homes.
A qualified heating and ventilating contractor should be
consulted.
Important:
Ventilation hoods and blowers are designed for use with
single wall ducting. However, some local building codes or
inspectors may require double wall ducting. Consult local
building codes and/or local agencies before starting to
assure that hood and duct installation will meet local
requirements.
Tools Needed
(2) 1/2” wrenches
1/8” (3.17mm) drill bit
3/16” (4.76mm) drill bit
12” Adjustable wrench
Hand or electric drill
Tape measure
Phillips & flathead screwdrivers
Marking instrument
Level
Furniture dolly
T-20 Torx screwdriver
Protective gloves
Items Not Included
Drywall/Concrete Anchors
Pipe Compound/Tape
Rope/Twine
3/4” (19mm) Flex Line
(2) NPT Flare Adapters
Range
Width
Range Top Configuration
Cubic Feet per Minute
(min requirement)
Ventilation Options
36"
4 burners with griddle
800 (cfm)
36” or 42” Pro Wall Hood
36” Custom Insert w/ optional blower
42” or 48” Island Hood w/ optional blower
6 burners
1100 (cfm)
48"
6 burners with griddle
1200 (cfm)
48” or 54” Pro Wall Hood
48” Custom Insert w/ optional blower
Important Notes:
It is recommended that a THERMADOR PROFESSIONAL
®
wall or island hood or custom insert is used with
THERMADOR PROFESSIONAL
®
Ranges. Refer to
www.thermador.com
for a complete selection of Professional
Ventilation options, Blowers, and Accessories.
* For high output gas ranges (60,000 BTU or greater), the minimum of one (1) CFM of ventilation per 100 BTU is
recommended. If the range has a griddle, add 200 CFM to the estimated blower capacity. Additional blower capacity may
be required for longer duct runs.
For island applications, it is recommended to use a hood width that exceeds the width of the range by 6” (152mm),
overlapping the range by a minimum of 3” (76mm) on each end.
CFM = “cubic feet per minute” (standard blower capacity rating).