TOSHIBA 6.19.6 Output Voltage Adjustment When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' of operation, the LCD screen displays the output voltage on the present output voltage adjust screen: OUTPUT VOLT. ADJUST OUTPUT VOLTAGE.=###% >F1:DATA SET MODE > Δ/∇ :PREV/NEXT SCREEN Press the F1 key to display the following active adjustment screen: OUTPUT VOLT. ADJUST REFERENCE ADJUST CHANGE DATA >ENTER: ACCEPT CHANGE The locations marked ## will show the numerical value of the allowable voltage adjustment parameter values. Press the 'up' and 'down' arrow keys to adjust the setting from between ±5 volts. This will cause the unit's output voltage to adjust to within ±2% of its nominal value. If the inverter is not running, and the output voltage cannot be adjusted; the following message will be displayed: OUTPUT VOLT. ADJUST ADJUST PROHIBITED DATA CANNOT CHANGE >Δ/∇:PRV/NEXT SCREEN Pressing the F1 key will have no effect on this display screen 6.19.7 Equalize Charge Mode Select Contact Toshiba Customer Support toll free at 1-877-867-8773 before using this option. DAMAGE to the battery system may occur if this option is used improperly. 4200FA CT/XT User's Manual 56