Tripp Lite 5P1500RC Eaton 5P750RC 5P1000RC and 5P1500RC UPS Installation and U - Page 10

Display functions, 6 User settings

Page 10 highlights

ENGLISH 2.5 Display functions Press the Enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll through the menu structure. Press the Enter ( ) button to select an option. Press the button to cancel or return to the previous menu. Main menu Measurements Submenu Display information or Menu function Load W VA / Load A pf / Output V Hz / Input V Hz / Battery V min / Efficiency / Power usage Control Load Segments Start battery test Reset fault state Restore factory settings Reset power usage Group 1: ON / OFF Group 2: ON / OFF These commands overrule user settings for load segments. Starts a manual battery test Clears active faults Returns all settings to original values (UPS restart required) Clears power usage measurements Settings Fault log Identification Local settings In/Out settings On/Off settings Battery settings Fault list Reset fault list Sets product general parameters Sets Input and Output parameters Sets On/Off conditions Sets battery configuration Displays the faults stored Clears faults UPS Type / Part Number / Serial Number / Firmware release / Com card address 2.6 User settings The following table displays the options that can be changed by the user. Local settings Submenu Language LCD settings Audible alarm Output voltage Available settings Default settings [English] [Français] [Deutsch] [Español] [English] Português] [Italiano] [Simplified Chinese] [Japanese] Menus, status, notices and alarms, UPS User selectable when UPS is powered for the first time. fault, Event Log data and settings are in all supported languages. Modify LCD screen brightness and contrast to adapt to room light conditions . [Enabled] [Disabled on battery] [Always disabled] Enable or disable the buzzer if an alarm occurs. Enable [100V] [120V] [125V] User selectable when UPS is powered for the first time In/Out settings Input thresholds Sensitivity Load segments Auto start delay [Normal mode] [Extended mode] Extended mode reduces lower input voltage to 150 V before UPS transfers to battery. [High] [Low] High: for sensitive equipment, UPS will easily transfer to battery when utility conditions are becoming bad. [No Delay] [1 s] [2 s]... [65354 s] The connected load is powered after the specified delay. Normal mode High Group 1: 3 s Group 2: 6 s Load segments - Auto shutdown delay Overload prealarm [Disable] [0s] [1 s] [2 s]...[65354 s] During a power outage, authorises to keep some equipment running while turning off other equipment. [10 %] [15 %] [20 %] ... [100 %] [105 %] Gives a warning when a predefined critical percentage of load is Group 1: Disable Group 2: Disable [105 %] 5P 750VA-1.5 KVA US_EN Page 10

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23

Page 10
5P 750VA-1.5 KVA US_EN
ENGLISH
2.5 Display functions
Press the Enter
(
) button to activate the menu options. Use the two middle buttons (
and
) to scroll through the
menu structure. Press the Enter (
) button to select an option. Press the
button to cancel or return to the
previous menu.
Main menu
Submenu
Display information or Menu function
Measurements
Load W VA / Load A pf / Output V Hz / Input V Hz /
Battery V min / Efficiency / Power usage
Control
Load Segments
Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test
Starts a manual battery test
Reset fault state
Clears active faults
Restore factory settings
Returns all settings to original values (UPS restart required)
Reset power usage
Clears power usage measurements
Settings
Local settings
Sets product general parameters
In/Out settings
Sets Input and Output parameters
On/Off settings
Sets On/Off conditions
Battery settings
Sets battery configuration
Fault log
Fault list
Displays the faults stored
Reset fault list
Clears faults
Identification
UPS Type / Part Number / Serial Number / Firmware release /
Com card address
2.6 User settings
The following table displays the options that can be changed by the user.
Submenu
Available settings
Default settings
Local settings
Language
[English] [Français] [Deutsch] [Español]
[
Русский
] [Português] [Italiano]
[Simplified Chinese] [Japanese]
Menus, status, notices and alarms, UPS
fault, Event Log data and settings are in
all supported languages.
[English]
User selectable when UPS is
powered for the first time.
LCD settings
Modify LCD screen brightness and
contrast to adapt to room light
conditions .
Audible alarm
[Enabled] [Disabled on battery]
[Always disabled]
Enable or disable the buzzer if an
alarm occurs.
Enable
In/Out settings
Output voltage
[100V] [120V] [125V]
User selectable when UPS
is powered for the first time
Input thresholds
[Normal mode] [Extended mode]
Extended mode reduces lower
input voltage to 150 V before UPS
transfers to battery.
Normal mode
Sensitivity
[High] [Low]
High: for sensitive equipment, UPS will
easily transfer to battery when utility
conditions are becoming bad.
High
Load segments -
Auto start delay
[No Delay] [1 s] [2 s]… [65354 s] The
connected load is powered after the
specified delay.
Group 1: 3 s
Group 2: 6 s
Load segments
- Auto shutdown
delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage, authorises
to keep some equipment running
while turning off other equipment.
Group 1: Disable
Group 2: Disable
Overload prealarm
[10 %] [15 %] [20 %] ... [100 %]
[105 %]
Gives a warning when a predefined
critical percentage of load is
[105 %]